Undo the appointment of an RF room thermostat to the CH boiler.
•
Press the reset
button of the unit for approximately 5 seconds to
access the RF room thermostat menu of the CH boiler.
•
Press the service
button 2x. On the display above the
C
will be shown.
•
Press the reset
button of the unit again to remove the existing
appointments. The display of the unit will show rF again, with a flashing
-
L /
. If required, an RF room thermostat can be appointed to the unit
again.
•
Press the reset
button of the unit to exit the RF room thermostat menu
or wait for 1 minute.
5.3.4
Outdoor temperature sensor
The unit is provided with a connection for an outdoor temperature sensor. The
outdoor temperature sensor should be used in combination with an on/off room
thermostat.
In principle, any on/off room thermostat can be combined with an outdoor sensor.
Upon request of the room thermostat, the boiler will provide heat until the maximum
set temperature in the boiler has been reached. This maximum set temperature is
automatically regulated via the outdoor sensor, in accordance with the set fuel line
in the boiler.
Connect the room outdoor sensor (see par. 10.2).
For the fuel line setting, see the weather dependent regulation (see par. 0).
5.4
Connecting gas
1.
Fit the gas valve directly on the 1/2" gas connection of the connection set
using appropriate seal.
2.
Place a gas sieve in the connection for the unit if the gas may be
contaminated.
3.
Connect the gas pipe in the gas valve using appropriate seal.
4.
Check the gas carrying parts for leakages at a pressure of up to 50 mbar.
5.
The gas pipe should be fitted pressure free.
Daikin Europe NV
button, a
20