Technische Angaben
Stromversorgung
AKO-16523 / AKO-16523P / AKO-16523D.................................230 V~ ± 10%, 50 ± 5%
AKO-16520 / AKO-16520P ................................................120 V ~ + 8% - 12%, 50 ± 5%
Max. Leistungsaufnahme in der Steuerung..................................................................................................6.3 VA
Max. Nenn-Stromstärke .................................................................................................................................15 A
Relais SSV / DEFROST - SPDT - 20 A NO ............................................................ (EN60730-1: 15 (15) A 250 V~ )
Relais FAN - SPST - 16 A ........................................................................................(EN60730-1: 12 (9) A 250 V~)
Relais COOL - SPST - 16 A ......................................................................................(EN60730-1: 12 (9) A 250 V~)
Relais AUX 1 / H.CRANK. - SPDT - 20 A NO .........................................................(EN60730-1: 15 (15) A 250 V~)
Relais AUX 2 - SPDT - 16 A NO..............................................................................(EN60730-1: 12 (9) A 250 V~)
Schaltschütz - 20A (AKO-16523D) AC1 ..............................................................................20 A 400 V~ (III+N)
Anzahl der Relaisoperationen ............................................................................EN60730-1:100.000 Operationen
Temperaturbereich des Fühlers ...............................................................................................-50.0 ºC bis 99.9 ºC
Auflösung, Einstellung und Differenzwert ....................................................................................................0.1 ºC
Temperaturmessgenauigkeit ........................................................................................................................±1 ºC
Toleranz des NTC-Fühlers bei 25 °C ..........................................................................................................±0.4 ºC
Eingang für NTC-Fühler ......................................................................................................................AKO-14901
Arbeitstemperaturbereich...............................................................................................................-5 ºC bis 40 ºC
Lagerumgebungstemperatur ........................................................................................................-30 ºC bis 60 ºC
Schutzgrad ...................................................................................................................................................IP 65
Installationsklasse .......................................................................................................................II s/ EN 61439-1
Verschmutzungsgrad ...................................................................................................................II s/ EN 61439-1
Doppelte Isolierung zwischen Stromversorgung, Sekundärschaltkreis und Relaisausgang.
MODBUS-Adresse................................................................................................Auf dem Typenschild angegeben
Abmessungen ........................................................................................290 mm (B) x 141 mm (H) x 84.4 mm (T)
Interner Summer
NC ..............................................................(EN60730-1: 15 (13) A 250 V~)
NC..........................................................(EN60730-1: 15 (13) A 250 V~)
NC ..............................................................................(EN60730-1: 10 (8) A 250 V~)
AC3 ................................................................................9 A 400 V~ (III+N)
37
1652H311 Ed.01