User Manual
Attention hazardous through electric shock. Also with disconnection of this unit from the mains, hazardous
voltage still may be accessible through supply from battery. The battery supply should be therefore
disconnected in the plus and minus pole at the quick connectors of the battery when maintenance or service
work inside the UPS is necessary.
CAUTION! Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries
and the required precautions. Keep unauthorized personnel away from batteries.
CAUTION! When replacing the batteries, use the same number and type of batteries.
CAUTION! Internal battery voltage is 12VDC. Sealed, lead-acid, 6-cell battery.
CAUTION! Do not dispose of batteries in a fire. The battery may explode. Do not open or mutilate the battery
or batteries. Released electrolyte is harmful to the skin and eyes.
CAUTION! Unplug the UPS prior to cleaning and do not use liquid or spray detergent.
CAUTION! A battery can present a risk of electric shock and high short circuit current. The following precaution
should be observed before replacing batteries:
1) Remove watches, rings, or other metal objects.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or disconnecting batteries terminal.
Before installation, please make sure nothing inside of package is damaged. To protect your equipment
from power failure, be sure that power switch must be kept in the "ON" position. Following below steps to
install your UPS unit.
Placement & Storage Conditions
Install the UPS in a protected area that is free of excessive dust and has adequate air flow. Please place the
UPS away from other units at least 20 cm to avoid interference. Do NOT operate the UPS where the
temperature and humidity is outside the specific limits. (Please check the specs for the limitations.)
Connect to Utility and Charging
Plug in the AC input cord to the wall outlet. For the best results, suggest to charge the battery at least 4 hours
before initial use. The unit charges its battery while connecting to the utility.
Connect the Loads
Plug in the loads to output receptacles on the rear panel of the UPS. Simply turn on the power switch of UPS
unit, then devices connected to the UPS will be protected by UPS unit.
CAUTION: NEVER connect a laser printer or scanner to the UPS unit. This may
cause the damage of the unit.
❹Connect Modem/Phone/Network for Surge Protection (Only for the model with RJ-11/RJ45)
Connect a single modem/phone line into surge-protected "IN" outlet on the back panel of the UPS unit. Connect
from "OUT" outlet to the computer with another phone line cable.
❺Connect Com. Port and Install Software (only for the model with RS-232/USB port)
To enable remote UPS shutdown/start-up and status monitoring, connect the communication cable from the
USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed,
you can schedule UPS shutdown/start-up and monitor the UPS status.
Turn On/Off the Unit
Turn on the UPS unit by pressing the power switch. Turn off the UPS unit by pressing again the power switch.
All manuals and user guides at all-guides.com
No LED display on the front
panel.
Alarm continuously
sounds when the
mains is normal.
When power fails, back-up time
is shorten.
The mains is normal but the
unit is on battery mode.
MODEL
CAPACITY
Input Voltage
Input Voltage Range
Output Voltage Regulation
Frequency Range (Batt. Mode)
Transfer Time
Waveform
4 hours
Battery Type & No
Charging Time
Dimension (DxWxH) mm
Net Weight (kgs)
Humidity
Noise Level
MODEL
CAPACITY
Input Voltage
Input Voltage Range
Output Voltage Regulation
Frequency Range (Batt. Mode)
Transfer Time
Waveform
Battery Type & No
Charging Time
Dimension (DxWxH)
Net Weight (kgs)
Humidity
Noise Level
Problem
Possible Cause
Low battery.
Battery fault.
The UPS is not turned on.
The UPS is overload.
The UPS is overload.
Battery voltage is too low.
Battery defect. It might
be due to high
temperature operation
environment, or improper
operation to battery.
Power cord is loose.
400
400VA/240W
12V/4.5Ahx1
LED: 279 x 101 x 142 / LCD: 300 x 101 x 142
LED
3.55
LCD
3.7
1000
1KVA/600W
12V/7Ah x 2
8.2
Solutions
Charge the UPS at least 6 hours.
Replace the battery with the same type of
battery.
Press the power switch again to turn on
the UPS.
Remove
some
loads
first.
Before
reconnecting equipment, please verify
that the load matches the UPS capability
specified in the specs.
Remove some critical load.
Charge the UPS at least 6 hours.
Replace the battery with the same type of
battery.
Reconnect the power cord properly.
600
800
600VA/360W
800VA/480W
220/230/240VAC
162-290 VAC
± 10 % (Bat. mode)
50Hz +/-1 Hz
Typical 2-6 ms
Simulated Sine Wave
12V/7Ahx1
12V/9Ahx1
4-6 hours recover to 90% capacity
4.2
4.9
4.4
5.0
0-90% RH @ 0-40°C non-condensing)
Less than 40dB
1500
2000
1.5KVA/900W
2KVA/1200W
220/230/240VAC
162-290 VAC
± 10 % (Bat. mode)
50Hz +/-1 Hz
Typical 2-6 ms
Simulated Sine Wave
12V/9Ah x 2
12V/9Ah x 2
4-6 hours recover to 90% capacity
320 x 130 x 182
10.4
11
0-90% RH @ 0-40°C (non-condensing)
Less than 40dB