8. TYPE OF CONTROL
CONNECTION OF EXTERNAL ACCESSORIES
READ CAREFULLY
• When connecting external accessories, the power supply to the air curtain must be disconnected.
• All external control components must be connected according to the wiring diagram.
DS door contact
TECHNICAL INFORMATION
- Insulated switching contact with a maximum voltage of 230V, 6A
- IP67, can be connected as a connecting or disconnecting contact
CAUTION!
Not part of the delivery.
Door contact DK-1 / DK-B3
TECHNICAL INFORMATION
- Insulated switching contact with a maximum voltage of 12V.
Cable - Dual core cable with a diameter of 0.5 mm2 - Maximum length: 50 m.
CAUTION!
Not part of the delivery.
Thermostatic valve - TV1/1
TECHNICAL INFORMATION
- Thermostatic valve to regulate the water coil
- Can be used for all types of curtains with water coil
- Operates independently of the control regulation
CAUTION!
Not part of the delivery.
3-way valves - ZV-3 - 24V
TECHNICAL INFORMATION
- Zone valve to regulate the water exchanger 0 - 10V
- Cable - 4-wire with a cross-section of 1.5mm2. 24V / 50/60
delivery), control voltage 0-10V
CAUTION!
Not part of the delivery.
Ambient thermostat - TER-P
TECHNICAL INFORMATION
- Room thermostat for controlling the heating
- Cable - 2-wire with a cross-section of 1.5mm2, 230V/50Hz
CAUTION!
Not part of the delivery.
All manuals and user guides at all-guides.com
Hz power supply (24V external power supply - not included in
19
NT 1885 A - 08/2017