Remote push-button
A push-button can be connected to terminals 3 and 4 (shown as P1 on the wiring dia-
grams). It has the following function:
Test. By pressing the push-button for 4 seconds, the detector will emit a sound alarm and
the test function will be activated offering the possibility of testing all the visual and sound
alarms.
The test function includes the following steps:
Activation of the TEST by a BEEP
Red LED ON for 20 s
Yellow LED ON for 20 s
End of TEST operations by a BEEP
The green LED goes on flashing during all the test
By pressing the push-button for at least 8s, the detector will emit two acoustic signals and
the "alarm relay intervention" will also be tested.
Operation in alarm condition
When the device is switched on for the first time or after a long period of time with no
22