Télécharger Imprimer la page

AVE 45184/M Manuel D'instructions page 21

Publicité

Les langues disponibles

Les langues disponibles

All manuals and user guides at all-guides.com
Operating ambient relative humidity:
– reference = 65% ± 10% to 20°C ± 5°C
– range = 30% to 90%
Activation threshold for model 45184M:
– factory setting: 5000ppM ± 1000ppM, equal to 10% of the L.E.L.
– maximum permitted deviation under extreme temperature and humidity conditions:
2500ppM to 7500ppM, equal to 5% and 15% of the L.E.L.
Activation threshold for model 45184G:
– factory setting: 1860ppM ± 370ppM, equal to 10% of the L.E.L.
– maximum permitted deviation under extreme temperature and humidity conditions:
930ppM to 2790ppM, equal to 5% and 15% of the L.E.L.
Housing protection class : IP42
Possibility of connecting a remote push-button to carry out the detector operation test.
Standard compliance
Gas detectors 45184M and 45184G comply with standards CEI EN 50194 type A and CEI
EN 50270 type 1.
20

Publicité

loading

Ce manuel est également adapté pour:

45184/g