EPL and D2L Series
Field Installable Kits
Installation & Maintenance Information
APPLICATION
EPL and D2L Series panelboards provide a centrally controlled switching system
and short circuit protection for feeder or branch circuits to control lighting, heating,
appliances, heat tracing, motor and similar circuits. GFI and EPD options offer
personnel and equipment protection respectively.
EPL series panelboards are designed for use in Class I, Div. 1 and 2, Groups B
(with EPL GB KIT), C, D; Class II, Groups E,F,G, Class III hazardous areas as
defined by the National Electrical Code (NEC) and Canadian Electrical Code
(CEC) as well as in damp, wet locations - indoors or outdoors - with UL type 3, 4,
4X (with S752 or S753), 12.
D2L series panelboards are designed for use in Class I, Div. 2, Groups B (with
EPL GB KIT), C, D; Class II, Div. 2, Groups F & G; Class III.
FIELD INSTALLABLE KITS TABLE OF CONTENTS
A. Adding a circuit breaker (EPL HDL13; EPL HDL2)
B. Adding Group B Kit (EPL GB KIT)
C. Adding a space heater (EPL R22 KIT)
D. Adding an operator handle cover (EPL HG24 KIT; EPL HG36 KIT; EPL HG42 KIT)
E. Adding terminal housing mounting bracket (EPLA MTG KIT; D2LS MTG KIT)
F.
Adding a gland plate hub kit
FIELD INSTALLABLE KITS
A. Adding a circuit breaker (EPL HDL13; EPL HDL12)
Do not scratch or damage flat joint flame path on either cover or body.
Always clean both body and cover from dust and foreign particles prior to
closing. Dirt or foreign material must not accumulate on flat joint surfaces.
Personal injury or equipment damage can result from a compromised or
damaged flat joint flame path.
1.
De-energize panel, open circuit breaker enclosure and make sure bolts are
retracted in cover.
2.
Remove operator plug from desired position and install operator bearing.
3.
Install operator shaft assembly until fully seated. Now turn shaft counter
clockwise 2 to 3 turns. Operator pin must be pointing down.
4.
Install handle with screw and washer provided to shaft on the cover exterior.
5.
Remove actuator plate and install circuit breaker in desired location. NOTE:
Circuit breaker should be attached to chassis with torque of 30 lb-in. (0.21
m). See picture at bottom of page.
6.
Make sure to attach wire with appropriate torque value listed on circuit breaker.
If the panel is factory sealed, locate pre-labeled wire corresponding with circuit
breaker location and apply torque of 25 lb-in (0.17 N-m).
7.
Remove actuator strap from actuator plate assembly.
8.
Install and align slider in desired location and reattach actuator strap
9.
Reattach actuator plate assembly to chassis and close cover making sure the
flame path is clean and bolts are tightened to a torque of 40 to 45 lbs.-ft. (19.2
to 21.5 N-m)
10.
Following proper installation instructions in prior sections, attach conduit and
IF 1517 • 04/07
All manuals and user guides at all-guides.com
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
WARNING
Copyright © 2007, Cooper Industries, Inc.
CAUTION
Panelboards should be installed, inspected,
maintained, and operated by qualified and
competent personnel. Read entire
instructions before starting installation of
this product. Contact your Cooper Crouse-
Hinds Sales Representative, Cooper
Crouse-Hinds Customer Service or your
Cooper Crouse-Hinds Distributor if you
have any questions.
pull wire to desired terminal block.
11.
Make sure all loose wires are secured and will not be pinched between cover
and body when closing enclosure.
12.
Make sure all screws and bolts are tightened to the appropriate torque values
found in Chart 1 on page 2.
B. Adding Group B Kit (EPL GB KIT)
Do not scratch or damage flat joint flame path on either cover or body.
Always clean both body and cover from dust and foreign particles prior to
closing. Dirt or foreign material must not accumulate on flat joint surfaces.
Personal injury or equipment damage can result from a compromised or
damaged flat joint flame path.
1.
De-energize panel, open circuit breaker enclosure and make sure bolts are
retracted in cover.
2.
Remove actuator plate from housing as shown below.
N-
Actuator
Plate
Actuator
Strap
IF 1517
Page 1
Page 1
Page 2
Page 2
Page 2
Page 2
WARNING
Page 1

Publicité

loading

Sommaire des Matières pour Cooper Crouse-Hinds EPL Serie

  • Page 1 (with EPL GB KIT), C, D; Class II, Groups E,F,G, Class III hazardous areas as this product. Contact your Cooper Crouse- defined by the National Electrical Code (NEC) and Canadian Electrical Code Hinds Sales Representative, Cooper...
  • Page 2 Personal injury or equipment damage can result from a compromised or NOTE damaged flat joint flame path. Cooper Crouse-Hinds recommends attaching side gland plates with entries De-energize panel, open circuit breaker enclosure and make sure bolts are adjacent to the center gland plate.
  • Page 3 All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Cooper Crouse-Hinds "Terms and Conditions of Sale", and since conditions of use are outside our control, the purchaser should determine the suitability of the product for the intended use and assumes all risk and liability whatsoever in connection therewith.
  • Page 4 Cooper Crouse- (NEC) et le Code électrique canadien (CEC) ainsi que dans les endroits Hinds, le service à la clientèle de Cooper humides et mouillés - à l’intérieur ou à l’extérieur - avec type UL 3, 4, 4X Crouse-Hinds ou votre distributeur de (avec S752 ou S753), 12.
  • Page 5 Des blessures ou des dommages aux équipements peuvent résulter d’un chemin REMARQUE d’accès du joint plat de la flamme compromis ou endommagé. Cooper Crouse-Hinds recommande d’attacher le côté des plaques d’entrée avec Désactivez le panneau, ouvrez l’enceinte du disjoncteur et assurez-vous que des entrées adjacentes à la plaque d’entrée centrale.
  • Page 6 être régi par l’environnement et la fréquence d’utilisation. On recommande que ce soit fait au moins une fois par an. Cooper Crouse-Hinds recommande un programme d’entretien préventif électrique comme décrit dans le bulletin de l’Association nationale de protection contre les incendies NFPA 70B : Pratique recommandée pour...