Check code
Outdoor unit 7-segment display
Wired remote
controller display
01: PMV5
P16
P16
02: PMV6
03: SV7
P17
P17
P18
P18
0#: 4-way valves
1#: 4-way valve1
P19
P19
2#: 4-way valve2
*Put in outdoor unit No. in [#] mark.
P20
P20
1 : Compressor 1 side
P22
P22
2 : Compressor 2 side
1 : Comp. 1 side
P26
P26
2 : Comp. 2 side
1 : Comp. 1 side
P29
P29
2 : Comp. 2 side
P31
─
• For details about check codes determined with an Interface P.C. Board or an Inverter P.C. Board, refer to the Installation Manual of the outdoor unit.
*1 Inverter quantity information
(Super Modular Multi System e and u series (SMMS-e, SMMS-u, SHRM-u))
Fan
Comp. Inverter
Inverter
No.
1
2
1
2
01
Comp. 1
02
Comp. 2
03
Comp. 1 + Comp. 2
08
Fan1
09
Comp. 1 + Fan1
0A
Comp. 2 + Fan1
0B
Comp. 1 + Comp. 2 + Fan1
10
Fan2
11
Comp. 1 + Fan2
12
Comp. 2 + Fan2
13
Comp. 1 + Comp. 2 + Fan2
18
Fan1 + Fan2
19
Comp. 1 + Fan1 + Fan2
1A
Comp. 2 + Fan1 + Fan2
1B
All
: Inverter trouble
Trouble detected by central control device
Check code
Outdoor unit 7-segment display
Central control
device indication
C05
─
C06
─
C12
─
Differs according to trouble contents of unit with occurrence of alarm
P30
(L20)
─
S01
─
57-EN
Auxiliary code
Operation
—
—
—
—
Trouble
Wireless remote controller
Sensor block display of receiving unit
Auxiliary code
Operation
Timer
─
─
─
─
(L20 is displayed.)
─
– 29 –
Wireless remote controller
Sensor block display of receiving unit
Timer
Ready
Flash
ALT
Injection circuit trouble
ALT
Discharge temp. TD2 trouble
ALT
Discharge temp. TD3 trouble
ALT
4-way valve inverse trouble
ALT
High-pressure protective operation
Outdoor unit fan inverter trouble
ALT
ALT
IPM short protection trouble
ALT
Comp. position detective circuit system trouble
Other indoor unit trouble
ALT
(Group follower indoor unit trouble)
Ready
Flash
─
Sending trouble in central control device
─
Receiving trouble in central control device
─
Batch alarm of general-purpose equipment control interface
Group control follower unit trouble
• Duplication addresses of indoor units in central control device
• With the combination of air conditioning system, the indoor unit may detect the check code of L20
─
Receiving trouble in central control device
Check code name
Check code name
Judging device
I/F
I/F
I/F
I/F
I/F
Inverter
Inverter
Inverter
Indoor unit
Judging device
Central control device
Central control device
General-purpose
equipment I/F
Central control device
Central control device
58-EN