Applicable controls

REQUIREMENT
When the unit is used for the first time, it takes a while
for the remote controller to recognize operation input
after the power is turned on. This is not a malfunction.
Turning on the power the first time after
installation
It takes approximately 10 minutes until you can
operate the remote controller.
About 10 minutes
Remote
" "
controller
Power on
" " blinks
can be
turns off
used
Turning on the power from the 2nd time
onward
It takes approximately 3 minutes until you can
operate the remote controller.
About 3 minutes
Remote
controller
" "
Power on
" " blinks
can be
turns off
used
Normal settings were made when the indoor unit was
shipped from factory.
Change the indoor unit settings as required.
Use the built-in remote controller to change the
settings.
* The settings cannot be changed using the
wireless remote controller, simplified wired
remote controller, or remote-controller-less
system (for central remote controller only).
Basic procedure for changing
settings
Change the settings while the air conditioner is not working.
(Stop the air conditioner before making settings.)
The display content for setting differs from that on the former
types of remote controller (RBC-AWSU52-UL)
CAUTION
Set only the "Code(DN)ˮ shown in the following
table: Do not set any other "Code(DN)ˮ.
If a "Code(DN)ˮ not listed is set, it may not be
possible to operate the air conditioner or other
trouble with the product may result.
35-EN
1
In the "Field setting menu" screen, press
[
] and [
] to select "DN setting", and
then press [
Set/Fix]
2
Press [
] and [
] to select "Indoor
unit" or "Outdoor unit", and the press
[
Set/Fix]
If "Indoor unit" was selected, the fans and
lovvres of the indoor units operate.
When doing group connections:
The fans and louvres of the selected indoor
units operate.
3
Press [
] to black highlight the item code
(DN), and then press [
] and [
the item code
4
Press [
] to black highlight the data, and
then press [
] and [
] to set the data
5
After finishing setting the data of the item code
(DN), press [
Set/Fix]
"Continue?" is displayed.
6
To set the data of other item codes (DN), press
[
Set/Fix]
To not do other settings, press [
The changes are fixed, and the "Field setting
menu" screen returns.
" appears while data is changing.
"
When doing group connections:
Press [
Return] to open the unit selection
screen. In the unit selection screen, press [
Return] to briefly display "
", and then return to
the "Field setting menu" screen.
Installing indoor unit on high
ceiling
When an indoor unit is installed on a ceiling higher than
the standard height, make the high-ceiling setting for
fan speed adjustment.
Follow to the basic operation procedure
(1 → 2 → 3 → 4 → 5 → 6 ).
3,
• For the CODE No. in Procedure
specify [5d].
4
• Select the SET DATA for Procedure
"Height list of ceiling possible to be installed" table in
this manual.
– 18 –
Remote controller-less setting
Change the high-ceiling setting with the DIP switch on
the receiver section P.C. Board.
For details, refer to the manual of the wireless remote
controller kit. The settings can also be changed with
the switch on the indoor microcomputer P.C. Board.
* Once the setting is changed, setting to 0001 or 0003
is possible, however setting to 0000 requires a
setting data change to 0000 using the wired remote
controller (separately sold) with the normal switch
setting (factory default).
] to set
Return]
SET DATA
SW501-1
0000
OFF
(Factory default)
0001
ON
0003
OFF
To restore the factory defaults
To return the DIP switch settings to the factory defaults,
set SW501-1 and SW501-2 to OFF, connect a
separately sold wired remote controller, and then set
the data of CODE No. [5d] to "0000".
from the
SW501-2
OFF
OFF
ON
EN