Technical Data; Model Identification; Commissioning The Device - Madas EVO/NC Serie Manuel Technique

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2.0 - TECHNICAL DATA

• Use
• Room temperature (TS)
• Power voltages (see table 3a-3b)
• Power supply tolerance
• Electric wiring
• N° cycles/hours (versions without energy saving) :
• N° cycles/hours (versions with energy saving)
• Absorbed power
• Maximum operating pressure
• Closing and/or opening time
• Protection rating
• Class
• Mechanical resistance
• Rp threaded fittings
• NPT threaded fittings
• Filter element (on request)
• In compliance with
* Only single-phase, the device does not work if powered with three-phase voltage.

2.1 - MODEL IDENTIFICATION

EVO/NC
: Brass body
EVOF/NC
: Brass body + flow adjustment
EVOA/NC
: Aluminium body
EVOAF/NC
: Aluminium body + flow adjustment
2.2 - SIL LEVEL
The SIL level of the stand-alone solenoid valve is SIL 2; when two solenoids are installed in series and the relative seal test
(Valve Proving System), certified according to EN 1643, the achieved level is SIL 3, as set forth in EN 676:2008. The solenoid
valve has PL d level. For further data refer to the SIL LEVEL table (table 2).

3.0 - COMMISSIONING THE DEVICE

3.1 - OPERATIONS PRIOR TO INSTALLATION
• It is necessary to close the gas upstream of the valve prior to installation;
• Make sure that the line pressure DOES NOT EXCEED the maximum pressure declared on the product label;
• Any protective caps (if any) must be removed prior to installation;
• Valve pipes and insides must be clear of any foreign bodies;
• Make sure that the pipe thread is not too long, to prevent damaging the body of the device when screwing it on;
• In accordance with EN 161 a suitable filter must be installed upstream of a gas closing safety device;
• With outdoor installation, it is advisable to provide a protective roof to prevent rain from damaging the electrical parts of the device.
• Prior to carrying out any electrical wiring operations, make sure that the main voltage matches the supply voltage indicated
on the product label;
• Cut out power prior to proceeding with wiring;
• According to the plant geometry, check the risk of explosive mixture arising inside the piping;
• If the solenoid valve is installed near other devices or as part of an assembly, compatibility between the solenoid
valve and this other device must be evaluated beforehand.
• Avoid installing the solenoid valve near surfaces that could be damaged by the coil temperature;
• Provide a protection against impacts or accidental contacts if the solenoid valve is accessible to unqualified personnel.
Madas Technical Manual - 1|1.1 - REV. 1 of 6
: non-aggressive gases of the three families (dry gases)
: -20 ÷ +60 °C (230 Vac with energy saving
: 12Vdc - 12 V/50 Hz - 24 Vdc - 24 V/50 Hz - 110 V/50-60 Hz - 230 V/50-60 Hz*
: -15% ... +10%
: cable gland M20x1,5
1800 (time ON 1s - time OFF 1s)
~
:
1000 (time ON 1s - time OFF 2,5s)
~
: see table 3a-3b
: 200 mbar
: <1 s
: IP65
: A
: Group 2
: (DN 10 - DN 15 - DN 20) according to EN 10226
: request feasibility
: metal net with filtering surface ≤ 1mm
: Regulation (EU) 2016/426 (Appliances burning gaseous fuels)
EMC Directive 2014/30/EU - LVD Directive 2014/35/EU - RoHS II Directive 2011/65/EU
9
Jul 2020
th
-20 ÷ +85 °C)
2
EVO.../NC - EVOA.../NC

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Evoa/nc serie

Table des Matières