Rs-485 Port; Connection To The Indoor Unit; Factory Reset; Digital Input - Airzone Aidoo Pro AZAI6WSP Serie Guide Rapide

Masquer les pouces Voir aussi pour Aidoo Pro AZAI6WSP Serie:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 20

RS-485 port

Modbus / BACnet
RS485 port for establishing Modbus/BACnet MS-TP
communication with the device.
The device can work as a Modbus slave or as a
BACnet MS-TP slave/master.
AZX6AIQBOXM - AIRQ box in-duct IAQ monitoring and controlling device
AZX6AIQBOXM

Connection to the indoor unit

This terminal allows the device to communicate with the indoor AC unit or the thermostat via
the connection cable, allowing management of the following parameters:
On/Off
Operation mode
Fan speed
Set-point temperature
Adjustment of slats (not available on all models).
As well as reading of room temperature reading and errors in the unit.
Both the shape of the terminal on the Aidoo Pro device and the shape of the cable may vary
depending on the compatible manufacturer.

Factory reset

This button allows you to restore the device to factory settings by pressing it continuously for
more than 10 seconds.

Digital input

Voltage free input. It can be used as a window contact, occupancy or similar to turn the AC unit
on/off if the input changes value.
By default it will be disabled and configured as "normally open."
Relay output (12 V) - Auxiliary heat
This output provides 12 Vdc through a relay. It offers control over a heat supply stage in
situations when the unit is unable to reach the setpoint temperature desired by the user.
By default it is disabled.
Device for air purification by ionization.
AZAI6WSPxxx