Re-setting the pressure regulator
Changes to the factory settings are the
performer's sole responsibility.
The pressure settings of the pressure regulator
can be adjusted as follows:
Relieve the pressure regulator by opening
(about 0.5 l/min) a tap 14 after the domestic
water station.
Use the Allen key 11 to
adjust the screw 12.
Turn the key clockwise to increase
and turn it counter-clockwise to
lower the secondary pressure.
A 360-degree turn of the key
corresponds to a change in
pressure of 30 kPa (0.3 bar).
Close the tap 14 after re-setting the pressure.
Allen key size: 6 mm.
The operating and maintenance instructions
11
are to be handed over to the home owner upon
+
delivery.
12
Check the pressure adjustment with
a pressure gauge at static pressure
(zero consumption).
Make sure that the pressure adjustment
complies with applicable guidelines,
regulations and standards.