Hubbell Adaptive Technology Wall Switch Sensor
DESCRIPTION
The Hubbell wall switch sensor is an intelligent self-adapting device that is
designed to replace existing wall switches.
SPECIFICATIONS
•
1000 sq. ft. coverage area (Models: AP and AD)
•
400 sq. ft. coverage area (Models: AU)
•
Single or Dual Circuit 120/277VAC, 50/60Hz operation
•
Electrical Ratings: (Each Output Separately)
120VAC – 800W Incandescent, 1000W Ballast, 1/4 HP 277
VAC – 1800W Ballast, 1/4 HP
24VDC- Low Voltage Module Rating
•
Adjustable Time Delay: 4-30 minutes, self-adapts based on occupancy
•
Light Level Adjustment (Circuit B output on Dual Circuit versions):
10 to 500FC
•
UL, cUL Listed
PRECAUTIONS
CAUTION: RISK OF ELECTRICAL SHOCK. Turn power off at service
panel before beginning installation. Never wire energized electrical
components.
CAUTION: USE COPPER CONDUCTOR ONLY
Read and understand all instructions before beginning installation.
NOTICE: For installation by a licensed electrician in accordance with
National and/or local Electrical Codes and the following instructions.
NOTICE: For indoor use only.
Confirm device ratings are suitable for application prior to installation.
Use of device in applications beyond its specified ratings or in applications
other than its intended use may cause an unsafe condition and will void
manufacturer's warranty.
NOTICE: Do not install if product appears to be damaged.
NOTICE: Connect to field wiring rated for 60°C or greater.
INSTALLATION
1. Turn power OFF at the service panel.
2.
Remove the old switch(es) if applicable.
3.
Wire as shown in the WIRING DIAGRAMS section. Figures 1 and 2
denote wiring method for Leakage to Ground Sensors (Note: A secure
ground is required for proper operation). Figure 3 denotes wiring
method for Neutral Wiring Sensors. Figure 4 represents wiring for low
voltage sensors (Note: Low voltage models require one CU300xx
module per output).
4.
Install sensor in wall box using mounting screws provided.
5.
Restore power to the sensor and allow it to initialize (up to 2 minutes).
6.
Sensor is factory configured to provide the most energy savings. If
additional adjustments are required, see the ADJUSTMENTS section.
7.
If daylight harvesting is desired, calibrate the sensor's photocell as
described in the PHOTOCELL CONTROL section.
8.
Install a decorator style wall plate (not included).
TEST MODE
1.
Make sure lights are ON
2.
Press and hold the ON/OFF button. Lights will cycle OFF then back
ON. Release the ON/OFF button.
•
For dual circuit sensors, press and hold the ON/OFF button for Circuit A.
•
For sensors without buttons, remove the cover (see ADJUSTMENTS
section) and press and hold the Test Button.
3.
Sensor is now in Test Mode (NOTE: While in Test Mode the sensor will
operate in Automatic ON/Automatic OFF mode). Vacate room; lights should
turn OFF after 5 seconds. Wait 5 seconds after turn OFF before re-entering
space. Step back into room, lights will turn back ON. Repeat walk test as
necessary to confirm sensor is operating and detecting in the area as desired.
Sensor will flash red and/or green LED while moving to indicate Passive
Infrared (PIR) or Ultrasonic occupancy detection respectively. NOTE: Sensors
with ultrasonic technology can be very sensitive and may require more than 5
seconds of no movement before turning lights off.
4.
To exit Test Mode, press any button.
NOTE: Sensor will automatically exit Test Mode after sixty (60) minutes.
Wiring Device-Kellems
Hubbell Incorporated (Delaware)
Shelton, CT 06484
1-800-288-6000
www.hubbell-wiring.com
PD2768
Page 1
Dual Technology / Passive Infrared / Ultrasonic
Installation and Operating Instructions
08/16
COVER RELEASE
CATCH
LINE A
BLACK
LINE B
VIOLET
PHOTOCELL
PUSH BUTTON
GROUND
CONNECTION
COVER RELEASE
CATCH
LINE CIRCUIT
BLACK
PHOTOCELL
PUSH BUTTON
GROUND
CONNECTION
COVER RELEASE
CATCH
LINE CIRCUIT
BLACK
PHOTOCELL
PUSH BUTTON
NEUTRAL
WHITE
GROUND
CONNECTION
COVER RELEASE
CATCH
PHOTOCELL
PUSH BUTTON
RED (30mA)
BLACK
BLUE (PRIMARY)
GRAY (SECONDARY)
WIRING DIAGRAMS
RED
LOAD 1
BUTTON A
FIGURE 1
(TEST BUTTON)
DUAL-TECH, DUAL
CIRCUIT, GROUND
BUTTON B
CONNECTION
BLUE
LOAD 2
RED
LOAD
FIGURE 2
DUAL-TECH, SINGLE
BUTTON A
CIRCUIT, GROUND
(TEST BUTTON)
CONNECTION
RED
LOAD
FIGURE 3
(TEST BUTTON
DUAL-TECH, SINGLE
LOCATED
CIRCUIT, NO BUTTON,
UNDER COVER)
NEUTRAL CONNECTION
BUTTON A
TEST BUTTON
YELLOW / WHITE (N.O.)
BLUE / WHITE (COMMON)
BLACK / WHITE (N.C.)
BUTTON B
FIGURE 4
DUAL-TECH, DUAL
CIRCUIT, LOW VOLTAGE
CONNECTION
English
®