HPZC10*
HYDRONIC PRO ZONE VALVE CONTROL PANEL
HPSR106 6-ZONE VALVE CONTROLLER
Zone 1
T-stat Call
Valve Open
DHW
Priority
PANEL SPECIFICATIONS
Model
Zones Transformers
HPZC103
3
(1) 24V 40VA
HPZC104
4
(1) 24V 40VA
HPZC105
5
(2) 24V 40VA
HPZC106
6
(2) 24V 40VA
1
Each transformer is protected with a 2 Amp replaceable fuse.
2
Transformers have a Class 2 output and are rated for 24V, 40VA at 25 °C. It is up to the installer to ensure that the 40VA
transformer rating is not exceeded.
3
All circulator relay connections are rated for 5A full load and 30A locked rotor (1/6 to 1/2HP depending on technology)
at 120VAC. Check circulator plate ratings to ensure full load current is not exceeded.
2
3
4
5
6
Power
Boiler
End Switch
Electrical
Rating for
Main Burner,
End Switch
Burner, and
Input
1
Power
Zones
120VAC,
24V, 1 A
60Hz, 1
120VAC,
24V, 1 A
60Hz, 1
120VAC,
24V, 1 A
60Hz, 1
120VAC,
24V, 1 A
60Hz, 1
INSTALLATION INSTRUCTIONS
WHAT'S IN THE BOX?
• Hydronic Zone Panel
• Mounting Hardware (3 Screws and 3 Wall Anchors)
• 2, 2-Amp Fuses
• Install Manuals (English & French)
CAUTION
1. Disconnect power supply before beginning
installation to prevent electrical shock or
equipment damage.
2. Use copper conductors only.
3. Use only NEC Class 1 wire for all line voltage
wiring connections. Class 1 wires must be
rated for at least 167 °F (75 °C).
4. For installation by professionals only.
Table 1.
Electrical
Rating for
Pump End
Switch and
2
3
Priority Pump
120 VAC
5FLA, 30LRA
120 VAC
5FLA, 30LRA
120 VAC
5FLA, 30LRA
120 VAC
5FLA, 30LRA
Type 1 Enclosure
Priority
Zone
Control
Width
Height Depth
Yes
10-1/4"
7-1/2"
Yes
10-1/4"
7-1/2"
Yes
11-3/4"
7-1/2"
Yes
11-3/4"
7-1/2"
33-00360EF-08
2-1/8"
2-1/8"
2-1/8"
2-1/8"

Publicité

Table des Matières
loading

Sommaire des Matières pour Honeywell Home HPZC10 Serie

  • Page 1 HPZC10* HYDRONIC PRO ZONE VALVE CONTROL PANEL INSTALLATION INSTRUCTIONS WHAT'S IN THE BOX? • Hydronic Zone Panel • Mounting Hardware (3 Screws and 3 Wall Anchors) • 2, 2-Amp Fuses • Install Manuals (English & French) HPSR106 6-ZONE VALVE CONTROLLER Zone 1 Power T-stat Call...
  • Page 2 HPZC10* MOUNTING Din Rail Flow 1. Mount the DIN rail as specified by DIN rail manufac- turer. Hang Hole Flow 1. Hang the panel on a wall-mounted screw. M37086A Fig. 4. 2. Hang panel by the tabs on the rail’s top edge. M37083A Fig.
  • Page 3: Wiring And Setup

    HPZC10* WIRING AND SETUP Standard Wiring Layout Below wiring diagrams represent a 6 zone valve panel and a 4 zone valve panel. Wiring diagrams for 5 and 3 zone valve panels are identical but with extra zones depopulated. THERMOSTAT THERMOSTAT WIRING WIRING TO BOILER NON-CONNECTED...
  • Page 4 HPZC10* Power Input Priority Override Resideo Hydronic Panels include a convenient wiring Resideo Hydronic Panels support priority operation and terminal for wiring 120V/60Hz/1Ph power. These can be enabled with the use of a switch located in the top terminals, found at the bottom right side of the panel, right section of the panel labeled "Priority Zone".
  • Page 5 HPZC10* Zone Valve Resideo Hydronic Panels are compatible with common 24V zone valves and can be wired as shown below or in the wiring diagrams on page 3. MOTOR MOTOR SWITCH SWITCH TWO WIRE ZONE VALVE MUST USE A JUMPER TWO WIRE ZONE VALVE THREE WIRE POWER OPEN SPRING...
  • Page 6 HPZC10* Boiler Controls Resideo Hydronic Panels are capable of managing boilers with DHW priority. The panel features two isolated end switches labeled Boiler and End Switch for TT outputs to the boiler. Two slide switches are available to provide simple programing of the end switches to meet the desired application.
  • Page 7: Regulatory Information

    HPZC10* TROUBLESHOOTING This panel provides a status indicator label which is available both when the panel cover is in place and removed. Descriptions of the indicator LED's are shown Valve Fuse Protection below: LED's T-stat Call indicate the thermostat associated with The Hydronic Zone Valve panels come equipped with that specific zone is calling for heat, with the exception of automatically resettable fuses on each valve output.
  • Page 8 33-00360EF—08 M.S. Rev. 07-19 | Printed in United States This product is manufactured by Resideo Technologies, Inc., Golden Valley, MN, 1-800-468-1502 ©2019 Resideo Technologies, Inc. The Honeywell Home trademark is used under license from Honeywell International Inc. All rights reserved.
  • Page 9 HPZC10* PANNEAU DE COMMANDE DE VANNES DE COMMANDE DE ZONE HYDRONIQUE PRO INSTRUCTIONS D’INSTALLATION CONTENU DE L’EMBALLAGE • Panneau de régulateurs de vannes de zone hydronique • Quincaillerie de montage (3 vis et 3 ancrages muraux) • 2 fusibles de 2 A •...
  • Page 10: Montage

    HPZC10* MONTAGE Rail DIN 1. Montez le rail DIN tel qu’indiqué par le fabricant du rail DIN. Trou de suspension 1. Accrochez le panneau à une vis fixée au mur. M37086A Fig. 4. 2. Suspendez le panneau par les languettes sur le bord supérieur du rail.
  • Page 11: Câblage Et Configuration

    HPZC10* CÂBLAGE ET CONFIGURATION Disposition standard du câblage Les schémas de câblage ci-dessous représentent un panneau de régulateurs de vannes à 6 zones et celui à 4 zones. Les schémas de câblage pour les panneaux à 5 zones et à 3 zones sont similaires. CÂBLAGE DU CÂBLAGE DU THERMOSTAT...
  • Page 12 HPZC10* Alimentation du panneau Dérivation prioritaire Les panneaux hydroniques Resideo comprennent une Les panneaux hydroniques Resideo offrent une fonction borne de câblage pratique pour une alimentation de prioritaire qui peut être activée à l’aide d’un interrupteur 120 V/60 Hz/1 Ph. Ces bornes, situées dans le côté situé...
  • Page 13 HPZC10* Vanne de zone Les panneaux hydroniques Resideo sont compatibles avec les vannes de zone de 24 V standards et peuvent être raccordés comme indiqué dans les schémas de câblage à la page 3. VANNE DE ZONE À 2 FILS UTILISATION D’UN CAVALIER REQUISE VANNE DE ZONE À...
  • Page 14: Contrôles De La Chaudière

    HPZC10* Contrôles de la chaudière Les panneaux hydroniques Resideo permettent de gérer les chaudières avec une priorité pour l’ECS. Le panneau est doté de deux interrupteurs d’extrémité isolés marqués « Chaudière et interrupteur d’extrémité » pour les sorties TT vers la chaudière.
  • Page 15: Dépannage

    HPZC10* DÉPANNAGE Ce panneau affiche un témoin d’état, que le couvercle soit placé ou non. Une description des témoins est fournie ci- dessous : Fusibles de protection de la vanne Le DEL « Demande du Thermostat » indique qu'il y a une Les panneaux sont munis d'un disjoncteur sur chaque demande de chauffage associé...
  • Page 16: Garantie Limitée De 5 Ans

    33-00360EF—08 M.S. Rev. 07-19 | Imprimé aux États-Unis Ce produit est fabriqué par Resideo Technologies, Inc., Golden Valley, MN, 1-800-468-1502 ©2019 Resideo Technologies, Inc. La marque de commerce Honeywell Home est utilisée sous licence avec l’autorisation d’Honeywell International Inc. Tous droits réservés.

Ce manuel est également adapté pour:

Hpzc103Hpzc104Hpzc105Hpzc106

Table des Matières