TABLEAU D'ALARME INCENDIE
ALARME
+
24 Vcc
Axxxx
TABLEAU D'ALARME INCENDIE
ALARME
FIN DE
4
LIGNE
ALARME
+
24 Vcc
Axxxx
1.1
BLINDAGE
3
TEST o i
NOTES SUR LE CÂBLAGE :
1 EN FONCTIONNEMENT NORMAL ET EN CAS D'ABSENCE DE DÉFAUT, LE RELAIS DÉRANGEMENT EST EXCITÉ
ET SES CONTACTS SONT NORMALEMENT FERMÉS.
2 LE RELAIS D'ALARME FEU EST NORMALEMENT DÉSACTIVÉ EN CAS D'ABSENCE DE DÉFAUT.
3 DES COMMUTATEURS DE TEST o i INDIVIDUELS (OU BIEN UN SÉLECTEUR DE DÉTECTEUR
AVEC UN COMMUTATEUR D'ACTIVATION) PEUVENT ÊTRE INSTALLÉS SUR LE TABLEAU INCENDIE.
LES COMMUTATEURS DE TEST NE SONT PAS FOURNIS.
4 SE RÉFÉRER AU CHAPITRE "CARACTÉRISTIQUES" POUR LES VALEURS DE RÉSISTANCE DE FIN DE LIGNE.
SE RÉFÉRER AU CHAPITRE "RÉSISTANCES FIN DE LIGNE" POUR LES DÉTAILS SUR L'INSTALLATION.
5
DES PRESSE-ETOUPE ET BOUCHONS METALLIQUES POUR ZONE DANGEREUSE CERTIFIES CORRECTEMENT
SONT REQUIS AFIN D'OCCUPER TOUTES LES ENTREES.
6
LE BLINDAGE DOIT ÊTRE CONNECTÉ AU PRESSE-ÉTOUPE MÉTALLIQUE. VÉRIFIER QUE L'ISOLANT EST RETIRÉ
Figure 7—Option de Câblage Ex d
AFIN D'ASSURER LA CONNEXION ÉLECTRIQUE ENTRE LE BLINDAGE ET LE BOÎTIER.
BLINDAGE
3
TEST o i
NOTES SUR LE CÂBLAGE :
1 EN FONCTIONNEMENT NORMAL ET EN CAS D'ABSENCE DE DÉFAUT, LE RELAIS DÉRANGEMENT
EST EXCITÉ ET SES CONTACTS SONT NORMALEMENT FERMÉS.
2 LE RELAIS D'ALARME FEU EST NORMALEMENT DÉSACTIVÉ EN CAS D'ABSENCE DE DÉFAUT.
3 DES COMMUTATEURS DE TEST o i INDIVIDUELS (OU BIEN UN SÉLECTEUR DE DÉTECTEUR
AVEC UN COMMUTATEUR D'ACTIVATION) PEUVENT ÊTRE INSTALLÉS SUR LE TABLEAU INCENDIE.
LES COMMUTATEURS DE TEST NE SONT PAS FOURNIS.
4 RÉSISTANCE DE FIN DE LIGNE FOURNIE AVEC LE TABLEAU D'ALARME INCENDIE.
5
DES PRESSE-ETOUPE ET BOUCHONS METALLIQUES POUR ZONE DANGEREUSE CERTIFIES CORRECTEMENT
SONT REQUIS AFIN D'OCCUPER TOUTES LES ENTREES.
6
LE BLINDAGE DOIT ÊTRE CONNECTÉ AU PRESSE-ÉTOUPE MÉTALLIQUE. VÉRIFIER QUE L'ISOLANT EST RETIRÉ
AFIN D'ASSURER LA CONNEXION ÉLECTRIQUE ENTRE LE BLINDAGE ET LE BOÎTIER.
Figure 8—Option de Câblage Ex d e
DÉTECTEUR X
9
mA +
8
mA + REF
COMMUN
COMMUN
7
2
FEU
FEU
2
6
N.O. FEU
N.O. FEU
2
5
N.F. FEU
N.F. FEU
COMMUN
COMMUN
4
1
DÉRANG.
DÉRANG.
N.O.
N.O.
3
1
DÉRANG.
DÉRANG.
2
24 Vcc +
1
24 Vcc –
DÉTECTEUR X 3301
mA +
9
8
mA + REF
COMMUN
COMMUN
7
2
FEU
FEU
2
6
N.O. FEU
N.O. FEU
2
5
N.F. FEU
N.F. FEU
COMMUN
COMMUN
4
1
DÉRANG.
DÉRANG.
N.O.
3
1
DÉRANG.
2
24 Vcc +
1
24 Vcc –
9
3301
19
mA –
LIBRE
29
18
mA – REF
LIBRE
28
17
27
COMMUN AUX
16
N.O. AUX
26
FIN DE
4
LIGNE
15
25
N.F. AUX.
14
RS-485 A
24
13
RS-485 B
23
o i MANUEL
12
22
24 Vcc +
11
24 Vcc –
24 Vcc –
21
mA –
LIBRE
19
29
18
mA – REF
LIBRE
28
COMMUN
17
27
AUX.
16
N.O. AUX
26
15
N.F. AUX.
25
14
24
RS-485 A
N.O.
13
RS-485 B
23
DÉRANG.
o i MANUEL
12
24 Vcc +
22
11
24 Vcc –
24 Vcc –
21
95-6704