Télécharger Imprimer la page

Thomas & Betts STX Serie Mode D'emploi page 4

Publicité

Les langues disponibles

Les langues disponibles

SECTION 4: USING PUTTY-TYPE SEALING COMPOUND SC65
Do not use SC65 for shielded cables or cables with 5 conductors or more including ground
1b. Spread insulated conductors slightly. Spread strands of uninsulated
grounding conductor where applicable (Figure 1b).
2b. Thoroughly mix the two parts of sealing compound until resulting mixture is
one uniform color (blue) without any streaks. Useable life is 30 minutes at
70
F (21
C)
o
o
CAUTION: DO NOT INSTALL SEALING COMPOUND BELOW 70
WARNING: AVOID PROLONGED CONTACT WITH SKIN. USE GLOVES
PROVIDED. DO NOT GET IN EYES. IMMEDIATELY WASH AREA WITH
PLENTY OF WATER.
3b. Apply small portion of sealing compound in the middle of insulated
conductors. Also apply compound between individual strands of
uninsulated grounding conductor. Bring conductors back together and
apply sealing compound all around conductors. Build up compound
approximately equal to the small inside diameter of the sealing chamber.
Length of compound plug should be approximately equal to the length of
the sealing chamber (Figure 2b)
4b. Slide sealing chamber onto cable and compound. Screw sealing chamber to
body sub-assembly until it completely seats on body. Remove any excess
compound (Figure 3b).
5b. Fill throat area of sealing chamber with compound. Use a suitable wooden
dowel to pack compound tightly around conductors (Figure 4b).
WARNING: REMOVE ALL EXCESS COMPOUND MATERIAL FROM OUTSIDE
OF SEALING CHAMBER WITH DAMP CLOTH. DO NOT USE ANY ABRASIVE
CLEANERS SUCH AS POWDER CLEANERS, SAND PAPER, STEEL WOOL OR
WIRE BRUSH THAT MAY DAMAGE THE FLAME PATH.
6b. Mount hub in desired location. Place encapsulated assembly into hub and
secure in position by tightening union until it bottoms (metal to metal
contact) (Figures 5b and 6b). Repack compound tightly around conductors if
required. Allow compound to set for approximately one hour before
disturbing conductors.
CSA CERTIFIED FOR FOLLOWING HAZARDOUS LOCATIONS
Class I Div. 1 & 2 Groups A,B,C,D.
Class II Div.1 & 2 Groups E,F,G.
Class III, SL (Integral seal), Type 4.
Hub size 1/2" to 3" Class I Div. 2: A,B,C,D, Class II Div.2: F,G; Class III, Type 4
Hub size 3 1/2" & 4" Class I Div. 2: B,C,D; Class II Div.2: F,G; Class III, Type 4
MADE IN CANADA
WARRANTY: Thomas & Betts sells this product with the understanding that the user will perform all necessary tests to determine the suitability
of this product for the user's intended application. Thomas & Betts warrants that this product will be free from defects in materials and
workmanship for a period of two (2) years following the date of purchase. Upon prompt noti cation of any warranted defect, Thomas & Betts
will, at its option, repair or replace the defective product. Misuse, misapplication or modi cation of Thomas & Betts Products immediately voids
all warranties.
Limitations and Exclusions: THE ABOVE WARRANTY IS THE SOLE WARRANTY CONCERNING THIS PRODUCT, AND IS IN LIEU OF ALL OTHER
WARRANTIES EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE, WHICH ARE SPECIFICALLY DISCLAIMED. LIABILITY FOR BREACH OF THE ABOVE WARRANTY IS LIMITED TO COST OF
REPAIR OR REPLACEMENT OF THE PRODUCT AND UNDER NO CIRCUMSTANCES WILL THOMAS & BETTS BE LIABLE FOR ANY INDIRECT, SPECIAL,
INCIDENTAL OR CONSEQUENTIAL DAMAGES.
© 2014 Thomas & Betts. All rights reserved.
Thomas & Betts Corporation, Memphis, Tennessee
Thomas & Betts Canada, St-Jean-sur-Richelieu, Quebec
www.tnb.ca
Figure 1b
F (21
C).
o
o
Figure 2b
Figure 3b
Figure 4b
Figure 5b
Figure 6b
TA01047 H
Page 4 of 4