D Ů L E Ž I T É B E Z P E Č N O S T N Í I N S T R U KC E
RIZIKO ZPĚTNOVAZEBNÍHO NAPĚTÍ, ODIZOLUJTE UPS INSTALOVÁNÍM
EXTERNÍHO ODDĚLOVACÍHO ZAŘÍZENÍ MEZI SÍŤOVÝ VSTUP A UPS;
PŘED PRACÍ NA TOMTO OKRUHU ZKONTROLUJTE NEBEZPEČNÉ NAPĚTÍ.
NEBEZPEČÍ
KE SNÍŽENÍ RIZIKA POŽÁRU BY SE JEDNOTKA MĚLA PŘIPOJIT POUZE
K OKRUHU POSKYTOVANÉMU S OCHRANOU PROUDOVÉ ODBOČKY PRO:
• D CURVE 10A RATING (UPSTREAM CIRCUIT), PRO MODELY 1 kVA (B / S),
• D CURVE 16A RATING (UPSTREAM CIRCUIT), PRO MODELY 2 kVA (B / S),
NEBEZPEČÍ
• D CURVE 20A RATING (UPSTREAM CIRCUIT), PRO MODELY 3 kVA (B / S).
VYSOKÉ SVODOVÉ PROUDY:
ZAJISTĚTE PŘIPOJENÍ ZEMNICÍHO VODIČE.
SPOLEČNÉ PŘIPOJENÍ ZDROJŮ VSTUP/VÝSTUP
NEBEZPEČÍ
PŘED PROVÁDĚNÍM JAKÉHOKOLIV PŘIPOJENÍ ZKONTROLUJTE, JESTLI
OCHRANNÁ ZAŘÍZENÍ PROTI PROUDU (NORMÁLNÍ ZDROJ AC A BOČNÍKOVÉ
ZDROJE AC) JSOU OTEVŘENY „0" (VYPNUTO).
VAROVÁNÍ
MŮŽE SE OBJEVIT KONDENZACE VODNÍ PÁRY, JESTLIŽE UPS JE ROZBALEN
PŘI VELMI NÍZKÉ TEPLOTĚ. V TAKOVÉM PŘÍPADĚ JE NUTNÉ POČKAT, AŽ UPS
BUDE ZCELA VYSUŠEN UVNITŘ I VENKU A TEPRVE POTOM POKRAČOVAT
S INSTALACÍ A POUŽÍVÁNÍM, ABY SE PŘEDEŠLO NEBEZPEČÍ ÚRAZU
ELEKTRICKÝM PROUDEM, PŘED INSTALACÍ POČKEJTE, AŽ UPS ZCELA
VAROVÁNÍ
VYSCHNE UVNITŘ I VENKU.
INDUKČNÍ ZÁTĚŽE (NAPŘÍKLAD MONITORY A LASEROVÉ TISKÁRNY) MAJÍ
PŘI SPUŠTĚNÍ VELMI VELKÝ ODBĚR ELEKTŘINY. JESTLIŽE JSOU PŘIPOJENY
K UPS, MUSÍ BÝT BRÁN V ÚVAHU ODBĚR PŘI SPUŠTĚNÍ TAKOVÝCH ZÁTĚŽÍ,
KDYŽ SE PROVÁDÍ VÝPOČET KAPACITY UPS, ABY SE PŘEDEŠLO PŘETÍŽENÍ
VAROVÁNÍ
A VYPNUTÍ UPS.
KVŮLI SNÍŽENÍ NEBEZPEČÍ POŽÁRU PŘIPOJTE UPS K OKRUHU VYBAVENÉMU
NADPROUDOVOU CHRANOU PROUDOVÉ ODBOČKY S AMPÉROVOU
HODNOTOU V SOULADU S NORMOU IEC/EN 60934 NEBO VAŠIMI MÍSTNÍMI
ELEKTRICKÝMI PŘEDPISY.
POZNÁMKA
DOPORUČENÍ NAJDETE V TECHNICKÝCH SPECIFIKACÍCH.
143