LERBAKKEN 10, 8410 RØNDE DENMARK
For safe installation of 9107B the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
For Installation in Zone 2 the following must be observed.
The 4501 programming module is to be used solely with PRelectronics modules. It is
important that the module is undamaged and has not been altered or modified in any way.
Only 4501 modules free of dust and moisture shall be installed.
9107BA:
9107BB:
Supply terminal (31,32)
Voltage:
Status Relay. terminal (33,34)
Voltage max:
Power max:
Current max:
Zone 2 installation:
Voltage max:
Power max:
Current max:
Installation notes:
In Class I, Division 2 installations, the subject equipment shall be mounted within a tool-secured
enclosure which is capable of accepting one or more of the Class I, Division 2 wiring methods
specified in the National Electrical Code (ANSI/NFPA 70) or Canadian Electrical Code (C22.1).
The equipment shall be installed in an enclosure with a minimum ingress protection rating of IP54
unless the apparatus is intended to be afforded an equivalent degree of protection by location.
The module is galvanically isolated and does not require grounding.
Install in pollution degree 2, overvoltage category II.
Use 60 / 75 ºC copper conductors with wire size AWG: (26-14)
In type of protection "intrinsic safety iD" the parameters for intrinsic safety for gas group IIB are
applicable.
Warning: Substitution of components may impair intrinsic safety.
Warning: To prevent ignition of the explosive atmospheres, disconnect power before servicing
and do not separate connectors when energized and an explosive gas mixture is present.
Warning: Do not install or remove modules from the Power Rail when an explosive gas mixture is
present.
Revision date:
2011-11-02
24
FM Installation drawing
HART
-transparent driver
1 channel
HART
-transparent driver
2 channel
19.2 – 31.2 VDC
125 VAC / 110 VDC
62,5 VA / 32 W
0.5 A AC / 0.3 ADC
32 VAC / 32 VDC
16 VA / 32 W
0.5 A AC / 1 ADC
Version Revision
V2 R0
9107 - Version de produit 9107-002
9107QF01
Prepared by:
PB
Page:
1/2