Product description

A
The
opening
detector
TRC301B
battery-powered KNX radio transmitter. It enables
the opening of a window or door to be signalled on
the bus. This information can also be used to
trigger a KNX command: set heating to frost
protection, raise the shutter, change scene etc.
The detector is equipped with :
• a built-in magnetic contact
• a connector block for connection of a remote
contact.
Functions
The TRC301B has an automatic function which can
send a KNX signal on each change of state of the
contact. According to the configuration effected,
1 or more pieces of information will be sent.
It is possible to override the automatic mode (e.g.
to open a window without switching off the
heating). To do this, press key A.
The indicator LED switches to red for 1 second.
To return the detector to Auto mode, press again
on key A; the indicator lamp changes to green for
1 second.
The specific functions of this product are defined in
its configuration and set-up.
Recommendations
Contact with the inside components may
damage the device due to static electricity
discharge.
• avoid hand contact, or by means of a metal
tool, with the electronic components or the
metal sections of the connector blocks.
• use nonmagnetic tools,
• before reaching the internal components,
discharge your static electricity by touching an
unpainted metal surface such as a water
pipeline or a grounded electrical device,
• do not make back-and-forth movements while
working on the inside component. If not
possible, repeat the above operations before
any new intervention on the product.
Opening
B
Unscrew the product using Phillips screwdriver.
1
Pull up the base guard.
2
Insert 2 alkaline batteries AAA LR03.
3
Battery change has no effect on product configu-
ration.
Fixing
Selection of location
The detector shall be located:
• Inside the building,
• Preferably fitted to the opening frame and at least
1m above the ground,
• Away from any source of interference (electrical
meter, metal mass...),
• On a plane surface.
When fixing on a metal frame, insert a 20mm
G
thick wood or plastic spacer between the
device base and the metal frame.
Fixing of detector
Fix the base using 2 screws suited to the
supporting materials or double-sided mounting
tape. If a remote contact is used, select a cable
grommet suitable for the cross-section of your
cable.
Cluster of cable grommets :
5
4 fixing options
is
a
Fixing of magnet holder
When the opening is closed, the magnet holder
shall be positioned opposite the opening built-in
contact with a clearance shorter than 5mm.
Align the magnet holder vertical notch opposite the
arrow located on the detector base.
Notch-arrow alignment
Side alignment and height adjustment are
G
required for correct operation of the detector.
Adjust magnet holder height according to the
diagram
. If necessary, use extra thickness
C
spacers supplied with the magnet holder or
insert a spacer under the opening detector (not
provided).
Fix the base plate of the magnet holder, fit the
magnet inside the guard and clip it onto the base
plate 2.
Clip then screw the
detector on its base
plate.
Fit the screw cover
(supplied on magnet
holder cluster) to the
guard cover.
Insert a small flat
screwdriver in
the notch provided to
remove the magnet
holder, then move it
in rotation.
Fixing and connecting of remote contact
See diagrams
and
C
E
The use of contacts D8931 and D8932 requires
G
connecting only blue and green wires.
Summary of opening and closing
distances
The built-in contact of the device uses such
distances between the multicontact detector and
the magnet to record any change of window
position (see attached table
Configuration
This transmitter may be configured in 3 different
ways :
• quicklink& : configuration without tool, see
User's Instructions supplied with the radio
transmitters.
• E-mode TX100/B V.2.7.0 or > : Description of
product
features
Manufacturer.
• S-mode ETS via TR131 : for ETS user, application
software STRC301B. Database and description
of software application available from the
Manufacturer.
Press
pushbutton once at TX100 learning
R
phase or for addressing in ETS. (See diagram
Input selection
(not available in quicklink& )
• Input 0 : opening detection - state indication
• Input 1 : function contact switch.
In configuration mode, the inputs are selected by a
short press of key
( > 5 seconds) for input 1.
G
C
Indicator operation
Empty batteries
Automatic mode
Window opening
5 mm
or closing
max.
Changing the mode
70 mm
by pressing key
Auto.→ Stop
Stop → Auto.
Remote contact
It is possible to connect a remote contact in order
to increase the capabilities of the detector(floating
contact, no voltage must be applied to the wired
inputs).
The two contacts (window + remote contact) are
handled as an "OR" logic function. To activate
detection by the remote contact, its window must
be activated at least once. To remove an already
active remote contact, the product must be reset
by removing the batteries for 30 sec.
Factory reset
Cover
Keep pushbutton
(>10s) then release it.
LED cfg turns off when factory reset is completed.
This
configuration. After factory return, wait 15s before
doing a new configuration.
Accessories
.
D8924 Projection opening contact with connector
D8931 Universal opening contact, protection,
D8932 Universal opening contact, protection,
Accessories not available in all markets. It is
possible to use other floating magnetic contacts
but operation is not guaranteed.
D
).
is
available
from
the
Hereby, hager Controls, declares that this radio opening
).
F
detector
requirements and other relevant provisions of low
voltage directives 2006/95/EC and CEM 2004/108/EC.
for input 0 and a long press
A
Product factory return is required to change
the configuration mode.
A
- Red flashing 1 sec.
- Orange flashing
1 sec. if no link is
configured
- Green flashing 100 ms if
link is configured
A
- Lit red 1 sec.
- Lit green 1 sec.
down until the LED flashes
R
operation
deletes
completely
block, wire.
white, wire.
brown, wire.
This device is to be installed only by a
professional electrician fitter according to local
applicable installation standards.
Conform to SELV installation rules.
Not to be installed outside.
å
Usable in all Europe
and in Switzerland
is
incompliance
with
The CE declaration can be consulted on the site :
www.hagergroup.net
product
the
essential
6T7992B