9
Checkliste
Kontroller før regulatoren tilsluttes
Checklist
Check before the regulator is connected
Prüfliste
Kontroller vor dem Regleranschluss
Liste de contrôle
Avant raccordement du régulateur, contrôler:
11
Klemme
Terminals
Pos.
Klemmen
Borne
1
1-2
2
35-36
3
77-78
4
24-25
5
25-26
EKS 65
Check
Check
Prüfen
Contrôler
Forsyningsspænding
20.4 V a.c. < U < 26.4 V a.c.
Supply voltage
20.4 V c.a. < U < 26.4 V c.a.
Versorgungsspannung
Tension d'alimentation
200 ohm/200°C < R
NTC
200 Ohm/200°C < R
PTC
S
2
S
1
Instructions RI.1D.C3.52 © Danfoss 09/95
Måleværdier
Measuring values
Messwerte
Valeurs de mesure
< 70 kohm/0°C
NTC
(20 kohm/23°C)
< 70 kOhm/0°C
NTC
(20 kOhm/23°C)
8 ohm < R < 20 ohm
8 Ohm < R < 20 Ohm
Fig. 10
Fig. 10
°C
ohm
0
1000.0
1
1003.9
2
1007.8
3
1011.7
4
1015.6
5
1019.5
6
1023.4
7
1027.3
8
1031.2
9
1035.1
10
1039.0
-10
11
1042.9
-11
12
1046.8
-12
13
1050.7
-13
14
1054.6
-14
15
1058.5
-15
16
1062.4
-16
17
1066.3
-17
18
1070.2
-18
19
1074.0
-19
20
1077.9
-20
21
1081.8
-21
22
1085.7
-22
23
1089.6
-23
24
1093.5
-24
25
1097.3
-25
26
1101.2
-26
27
1105.1
-27
28
1109.0
-28
29
1112.8
-29
30
1116.7
-30
35
1136.1
-35
40
1155.4
-40
45
1174.7
-45
50
1193.9
-50
10
12
°C
ohm
0
1000.0
-1
996.1
-2
992.2
-3
988.3
-4
984.4
-5
980.4
-6
976.5
-7
972.6
-8
968.7
-9
964.8
960.9
956.9
953.0
949.1
945.2
941.2
937.3
933.4
929.5
925.5
921.6
917.7
913.7
909.8
905.9
901.9
898.0
894.0
890.1
886.2
882.2
862.5
842.8
822.9
803.1
3