230 V a.c. or 115 V a.c. - See controller
0.5 VA
t
= 0 - +55°C
amb
Set temperature
1. Push the middle button until the tem-
perature value is shown
2. Push the upper or the lower button and
select the new value
3. Push the middle button to select the
setting.
Parameter
Function
Normal operation
Temperature (set point)
Thermostat
Differential
Display adjust
Compressor
Min. ON-time
Min. OFF-time
Defrost
Defrost stop temperature
Interval between defrost stats
Max. defrost duration
Displacement of time on cutin of defrost at start-up
Miscellaneous
Delay of output signal after start-up
Fault code
Sensor error
RI8KH583 12-2008
INSTRUCTIONS
EKC 100
Type = EKS 211
(5000 Ω / 25°C)
English
Manual start or stop of a defrost
• Push the lower button for 5 seconds.
Light emitting diode (LED)
• Relay is cut-in
Min.
Max.
Codes
value
value
---
-60°C
25°C
r1
1 K
20 K
r4
-20 K
20 K
c1
0 min
15 min
c2
0 min
15 min
d2
0°C
25°C / off 25°C / off
d3
0 hours
48 hours
d4
0 min
99 min
d5
0 min
15 min
o1
0 min
15 min
Er
U:
230 (115) V a.c. +10 / -15%
Relay
Rated voltage
I
(Derated 16 A relay)
Set menu
1. Push the upper button until a
parameter is shown
2. Push the upper or the lower button
and find that parameter you want to
change
3. Push the middle button until the
parameter value is shown
4. Push the upper or the lower button and
SW = 1.1X
select the new value
Factory
Actual
setting
setting
5. Push the middle button again to enter
the value. Time out 20 sec.
0°C
2 K
Start-up:
0 K
Regulation starts when the voltage is on.
0 min
0 min
Go through the survey of factory set-
tings. Make any necessary changes in the
respective parameters.
8 hours
45 min
0 min
0 min
Factory setting
If you need to return to the factory-set values, it can
be done in this way:
- Cut out the supply voltage to the controller
- Keep the upper and lower button depressed at the
same time as you recon nect the supply voltage
(115 V a.c.)
50/60 Hz
CE
UL
250 V
240 a.c.
10 (6) A
10 A Resistive
5FLA 30LRA

Publicité

loading

Sommaire des Matières pour Danfoss EKC 100

  • Page 1 INSTRUCTIONS EKC 100 230 V a.c. or 115 V a.c. - See controller 0.5 VA = 0 - +55°C (115 V a.c.) 50/60 Hz 230 (115) V a.c. +10 / -15% Relay Rated voltage 250 V 240 a.c. Type = EKS 211 (5000 Ω...
  • Page 2 - Couper la tension d’alimentation du régulateur. - Maintenir les boutons supérieur et inférieur enfoncés en remettant le régulateur sous tension. Instructions RI8KH583 © Danfoss 12/2008 The Product contains electrical components EKC 100 And may not be disposed together with domestic waste.