Ups Remote Control Functions - MGE Evolution S 1250 RT 2U Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Evolution
3.3
Return of AC Input Power
Following an outage, the UPS restarts automatically when AC input power returns (unless the restart function has been
disabled via UPS personalization) and the load is again supplied.
3.4
UPS Shutdown
3.5

UPS Remote Control Functions

Remote control connection and test
1. Check that the UPS is OFF and disconnected from the AC input source.
2. Remove connector (5) after unscrewing the screws.
3. Connect a normally closed volt-free contact (60 V DC / 30 V AC max., 20 mA max., 0.75 mm 2 cable
cross-section) between the two pins of connector (5) (see diagram).
4.
Plug connector (5) into the back of the UPS.
5.
Connect and restart the UPS following the previously described procedures.
6.
Activate the external remote shutdown contact to test the function.
Warning: This connector must only be connected to SELV (Safety Extra-Low Voltage) circuits.
3 — 2
All manuals and user guides at all-guides.com
24
ROO
RPO
Press button (24) for approximately 2 seconds.
The devices connected to the UPS are no longer
supplied.
Evolution offers a choice between two remote control
functions.
RPO: Remote Power OFF allows a remote
contact to be used to disconnect all the
equipment connected to the UPS. Restarting the
UPS requires manual intervention.
ROO: Remote ON/OFF allows remote action of
button (24) to shut down the UPS.
These functions are obtained by opening of the contact
connected between the appropriate pins of connector
(5) on the rear panel of the UPS (see figures below).
Contact open: UPS shutdown
Contact closed: UPS start-up (UPS connected to AC
power and AC power is available).
Note: The local ON/OFF control using button (24)
overrides the remote-control function.
Contact open: UPS shutdown, LED (26) goes ON.
To return to normal operation, deactivate the remote
external contact and restart the UPS by pressing but-
ton (24).
Operation
E N G L I S H
86-81710-00 A01

Publicité

Table des Matières
loading

Table des Matières