6. Control and functions
Each receiver can receive up to a maximum of 32 transmitters, switches or sensors. Upon
allocating on the selected output the first transmitter or sensor, the operating mode is defined.
The operating mode cannot be changed until all the transmitters (the two outputs) have been
cleared using the CLR button.
Switch mode: Each transmitter can be used to change the switching state, of the associated
output of the receiver. It is possible to switch ON (button I) with a switch and OFF (button O)
with another switch.
Window contact mode (D5-00-01): If at least one of the window contacts is open, this
activates ON the associated output of the receiver. If all possible window contacts are closed,
the associated output of the receiver is OFF. The window contacts transmit a signal
approximately every 15 minutes. 60 minutes after receipt of the last signal received, the
receiver considers this contact closed.
6.1 Compatible transmitters
The following transmitters can be associated with the receiver
Designation
Switch
10020001, 10020019, 10020022
Key card
Window Handle
Window contact
Dry contact sensor
Occupancy Sensor
(*) For more details see Communication Profiles – EEP available at:
www.enocean-alliance.org/what-is-enocean/specifications/
(**) N.B.! Only receivers with a serial number greater than or equal to 2002A0001 are
compatible with this EEP Profile.
6.2 Transmitter associated functions (switch mode)
The functions associated with different sensors are determined during learning. The learning
process (Cf § 5.1) is to do before activating the transmitter.
Designation
Switch
Button 1 (2, 3 or 4):
pressed and released before
visual acknowledge**
1
3
1
Button 1 (2, 3 or 4):
2
2
4
pressed then released after
visual acknowledge**
Button 1 (2, 3 or 4):
pressed and released before
visual acknowledge** followed by,
pressed then released after
visual acknowledge**
Key card
Card inserted before the entry into
learning mode, removed (in
learning mode) then reinserted
Window handle
Closed to opened or opened to
closed
Windows contact
Press the LEARN button
Dry contact sensor
Press the LEARN button
Occupancy sensor
Press the LEARN button
Note *: The ON state corresponds to the lighting of the LED (on the front of the product), contact
closure output NO and the opening of the output contact NF.
Note **: The visual acknowledge corresponds to holding the LED on or off for 4 seconds.
TOC11908NUcc_0120
0
LINE 10020070:
2
EEP Profile*
0
LINE reference
2
F6-02-01
10020067
F6-04-01
10020011
F6-10-00
10020032, 10020042
D5-00-01
10020047, 10020057
D5-00-01
A5-07-01,
10020051
A5-07-03**
Learning
Function obtained*
Button 1 (or 3): ON
Button 2 (or 4): OFF
Button 1 (2, 3 or 4):
Transition from ON to
OFF and vice Versa
(Switch mode only §6)
Button 1 (2, 3 or 4):
pressed
released : OFF
Card inserted: ON
Card removed: OFF
Tilt to opened: no
change
Opened to tilt: no
change
Closed to opened: OFF
Opened to closed: ON
Magnet away: ON
Magnet near: OFF
Contact closed: OFF
Contact open: ON
Detection (PIR = On):
ON
Detection (PIR = OFF):
OFF
7. Troubleshooting
7.1 New or existing installation
• Check the circuit breaker, the electrical supply and the load connected to the receiver
associated with this sensor (qualified electricians).
• Check the connected load and the connecting cables (qualified electricians).
• If the receiver functions at a shorter distance relative to the sensor, it is subject to interference
or used outside the transmission range.
• Search the system environment for changes that could cause the interference (for example
movement of metallic cabinets, furniture or partitions).
• Use the sensor or receiver in a more suitable location.
• Clear the receiver and perform a new learn process.
7.2 Automatic activation of the receiver
• The cause may be the activation of a sensor external to the system which has by chance
been programmed on the receiver.
• Clear the receiver and perform a new learn process.
7.3 Limitation of the range of the radio signals
• Transmitter/receiver used close to metallic objects or close to materials containing metallic
elements. Observe a distance of at least 10cm.
• Humidity in the materials.
• Device emitting high frequency signals such as: audio and video systems, computers,
electronic ballasts or fluorescent tubes. Observe a distance of at least 0,5m.
7.4 Contacts
E-mail: ............................
8. Declaration of conformity
This product can be marketed and distributed in the countries of the European Union. Hereby
0
TRI
SYS declares that radio equipment 10020070 is in compliance with directive 2014/53/EU,
2
known as the RED Directive.
The full text of the EU declaration of conformity is available at the following internet address: