3. Installation
3.8 Input and Output Transformer Connections
WARNING: The input transformer (T-in) output neutral is not bonded to chassis ground. Please
provide a means to connect the transformer chassis ground to the transformer output neutral.
Note: The transformer chassis ground must be connected to earth ground.
IMPORTANT: You may view and/or download this manual from the tripplite.com website to view
the cable connections in colors.
Figure 3-8: UPS
Note: Transformer input is Delta 3-Wire (3Ph + Ground) and
Transformer Cabinet
output transformer is Wye 4-Wire (3Ph + N + Ground).
13