English
PTH-3XXX-DF is a series of electronic pressure
transmitters designed primarily to measure total
and differential pressures in ventilation systems.
When used together with a standard aperture,
the pressure transmitter can also measure
air flow as a formula for converting differen-
tial pressure to air flow is incorporated in the
transmitter. The pressure transmitter is used for
monitoring, control and regulation purposes via
a controller, PLC or monitoring system.
Typical applications include:
- The maintenance/control of constant pressure
at a given position within the ventilation duct
system.
- The maintenance/control of desired under-
pressure within the ventilation duct system.
- Differential pressure measurement across
ventilation filter for optimum filter replacement.
- Volume flow determination via differential
pressure measurement across a standard
aperture.
PRODUCT PROGRAMME
Type
Product
PTH-3202-DF
Pressure transmitter, 0-2500 Pa,
display, flow
FUNCTION
PTH is a pressure transmitter for comfort
ventilation systems. It provides an active current
or voltage signal proportional to the measured
air pressure. If the pressure transmitter is set
for flow measurement, differential pressure
(Δp) is converted to volume flow (qv) using the
following formula: qv = k•√Δp. PTH consists
of a semiconductor pressure element with no
air throughput, thus protecting the unit against
dust in the ventilation system. The pressure
element is temperature compensated to provide
accurate pressure measurement throughout the
specified temperature range.
The required measurement range of the pres-
sure transmitter is set using three push buttons.
The buttons are also used to set the k-factor to
be used for flow calculation. Pressure or flow
is selected by simply changing a DIP switch
setting and replacing Pa with m3/h, m3/s or l/s
on the front cover.
By selecting flow range P, PTH pressure trans-
mitters can directly replace pressure transmit-
ters with existing square root output and flow
display in %.
The screw terminals of the pressure transmitter
can provide a 0/2 - 10 V output signal and/or a
0/4 - 20 mA output signal (see fig. 3).
The 0-10 V output signal is provided by terminal
2 with DIP 1 of SW1 in position "Off".
The 2-10 V output signal is provided by terminal
2 with DIP 1 of SW1 in position "On".
The 0-20 mA output signal is provided by termi-
nal 4 with DIP 1 of SW1 in position "Off".
The 4-20 mA output signal is provided by
terminal 4 with DIP 1 of SW1 in position "On"
(see figs 3 & 8).
A DIP switch allows two different damping times
to be selected so that pressure fluctuations
within the ventilation system are attenuated in
the transmitter output signal. If the actual pres-
sure / flow is outside the selected measurement
range, the display flashes.
CE MARKING
OJ Electronics A/S hereby declares that the
product is manufactured in accordance with
Council Directive 92/31/EEC on electromagnetic
compatibility (and subsequent amendments)
and Council Directive 73/23/EEC on electrical
equipment designed for use within certain
voltage limits.
APPLIED STANDARDS
EN 61000-6-2 and EN 61000-6-3
TECHNICAL DATA PTH-3202-DF
Full-scale pressure range 0 - 2500 Pa
Measurement ranges,
pressure
-50.0.. + 50.0 Pa,
0.0.. + 100.0 Pa,
0.0.. + 150.0 Pa,
0.0.. + 300.0 Pa,
0.0.. + 500.0 Pa,
0.0.. + 1000 Pa,
0.0..1600 Pa
© 2020 OJ Electronics A/S
Measurement ranges,
flow
1.00 m³/s, 3.00 m³/s,
5.00 m³/s, 10.00 m³/s,
30.00 m³/s, 50.00 m³/s,
100.0 m³/s, 100.0 m3/h,
300.0 m3/h, 500.0 m3/h,
1000 m3/h, 3000 m3/h,
5000 m3/h, 9999 m3/h,
30.00 m3/h x 1000,
50.00 m3/h x 1000,
99.99 m3/h x 1000.
m3/h can be replaced
by l/s or m3/s.
Square root output
In the flow range P,
differential pressure is
measured as % of
full-scale pressure
range using square root
calculation.
k-factor
0.001 to 9999
TECHNICAL DATA
Supply voltage ...................24 V~/=, ± 15%, 50/60 Hz
Power consumption ........................................... 0.5 W
Output ...............................................0-10 V=, 2-10 V=
0-20 mA, 4-20 mA
Accuracy*
PTH-3202.....1.5 %×MV*+0.3 %×SR*+2.5 Pa
Maximum pressure PTH-3202...30 kPa
Maximum load
0 – 10 V= ...........................................................>2.5kΩ
0 – 20 mA ........................................................ <=450Ω
Dampening (selectable) ............................0.4 s or 10 s
Housing dimensions (h×w×d) ...........91 × 75 × 38mm
Cable dimension ..........................................ø3-10 mm
Connection
PTH-3202 .................... 4 x Screw term, max 1.5mm²
Pressure tubes .........................................2 × ø6,2 mm
Environment data
Operating temperature -20°C to +40°C (continuous)**
Operating humidity ...................... 10%RH to 95%RH,
Operating altitude ........................................... ≤2000m
Enclosure rating .....................................................IP54
Weight ..................................................................110 g
*Note: MV = Measured Value / SR = Set measuring
range
**Note: Ambient temperature affects the LCD
display speed and contrast
non-condensing

Publicité

loading

Sommaire des Matières pour OJ Electronics PTH-3202-DF

  • Page 1 Pressure transmitter, 0-2500 Pa, CE MARKING Enclosure rating .............IP54 display, flow OJ Electronics A/S hereby declares that the Weight ..............110 g product is manufactured in accordance with *Note: MV = Measured Value / SR = Set measuring Council Directive 92/31/EEC on electromagnetic...
  • Page 2 OJ and the OJ logotype are trade- urement range, the display flashes. The pressure labels to the front cover of the transmitter (see marks of OJ Electronics A/S. All rights reserved. tubes must be as short as possible and must figs 6 and 7).
  • Page 3 Le PTH doit être vissé sur une surface plane. Le flux d’air, la conversion de la pression différen- OJ Electronics A/S déclare que le produit sens de montage n’a aucune incidence sur le tielle en flux étant intégrée dans le transmetteur.
  • Page 4 · www.ojelectronics.com transmetteur mesure la pression plusieurs fois et la valeur moyenne de la période choisie est restituée au fil de l’eau par le signal de sortie du transmetteur. De cette façon, les variations de © 2020 OJ Electronics A/S...
  • Page 5 OJ ELECTRONICS A/S Stenager 13B · DK-6400 Sønderborg Tel: +45 73 12 13 14 · Fax: +45 73 12 13 13 oj@ojelectronics.com · www.ojelectroncis.com The trademark is registered and belongs to OJ Electronics A/S · © 2020 OJ Electronics A/S...