4.3 Precision and dephasing
NB : Intrinsic error as µ of output signal
n
200 A calibre
Intensity in A~
MN 08 - MN 09 - MN 10 - MN 11 - MN 12 - MN 13 - MN 14 - MN 15 - MN 38 - MN 39
Intrinsic error (1)
Dephasing
Intrinsic error (1)
Dephasing
Intrinsic error (1)
(1) + 0.5 mA (MN 08/09/10/11) or + 0.5 mV (MN 14/15) or + 5 mV (MN 12/13/38/39/60) or
+ 50 mV (MN 88/89)
n
200 A calibre
Intensity in A~
Intrinsic error (1)
Dephasing
Intrinsic error (1)
Dephasing
(1) + 20 mA
(2) Unspecified
n
20 A calibre
Intensity in A~
Intrinsic error
Intrinsic error
n
10 A calibre
Intensity in A~
Intrinsic error
Dephasing
(1) + 0,1 mV
(2) Unspecified
n
2 A calibre
Intensity in A~
Intrinsic error
(1) + 2 mV
4.4 Conditions of use
The miniclamps must be used in the following conditions, in order to comply
with user safety and metrological performance requirements.
4.4.1 Overloads
Limit measuring time above 200 A.
Intensity
Operation
(1) With a frequency F < 1kHz and a peak factor Fc < 3
0.5 à 10 A 10 à 40 A 40 à 100 A 100 à 240 A
£ 3 %
£ 2.5 %
(2)
£ 5 °
MN 60
£ 3.5 %
£ 3 %
(2)
£ 6 °
MN 88 - MN 89
£ 5 %
£ 3 %
(2) Unspecified
0,1 à 1 A
1 à 20 A
MN 21
£ 5 % (1) £ 3 % (1) £ 1.5 %
(2)
(2)
MN 23 - MN 73
£ 3 % (3) £ 2 % (3)
(2)
£ 3 °
(3) + 200 mV
MN 38 - MN 39
MN 60
0.01 à 0.1 A
0.1 à 1 A
MN 71
£ 3 % (1)
£ 2.5 %
(2)
£ 5 °
0.01 à 0.1 A
0.1 à 1 A
MN 73
£ 5 % (1)
£ 3 % (2)
(2) + 1 mV
I < 200 A~
Permanent (1)
11
£ 2 %
£ 3 °
£ 2,5 %
£ 4 °
£ 2 %
20 à 80 A 80 à 150 A 150 à 200 A
£ 3 %
£ 2 °
£ 1 %
£ 3 %
£ 2 °
£ 3 °
0.1 à 20 A (24 A maxi)
£ 1 % + 50 mV
£ 2 % + 50 mV
1 à 5 A
£ 1 %
£ 3 °
1 à 2 A
£ 1 %
200 A~ < I < 240 A~
10 min. ON
followed by 30 min. OFF
£ 1 %
£ 2.5 °
£ 1.5 %
£ 3 °
£ 2 %
£ 5 %
£ 3 °
£ 7 %
£ 4 °
5 à 12 A
2 à 2.4 A