7. TECHNICAL SPECIFICATIONS

Power input
Input voltage
Operating frequency
Power input
Power supply fuse (power supply and outputs)
Cables
Rigid or flexible wire (braided or with ferrule)
One-pole
Two-pole
Operating data
Software class
Operating mode EN 60 730
Inputs
Digital input H1
Very low safety voltage for clean contact
Low voltage contact
Voltage with contact open
Current with contact closed
Analogue input H1
Very low protection voltage
Range
Internal resistance
Input L
Internal resistance
Input sensors B1, B9
Permitted connection cables (copper)
Cross-section
Maximum length
Outputs
Output relay
Current range
Maximum starting current
Maximum current (for all relays)
Voltage range
Interface
LPB
Total length
Cable cross-section
BSB
Length of base unit - peripherals
Total length
Cable cross-section
AC 230 V (±10 %)
50/60 Hz
8 VA
max. 10 AT
-
0,5...2,5 mm
2
0,5...1,5 mm
2
A
1b (automatic operation)
-
-
-
DC 12 V
DC 3 mA
-
-
DC 0..10 V
> 100 kΩ
AC 230 V (±10%)
> 100 kΩ
B1=NTC
10kΩ
B9=NTC 1kΩ
-
mm
0,25
2
m
20
-
AC 0,02...2 (2) A
15 A per ≤1 s
AC 10 A
AC 24...230 V (for clean contact)
Connection with 2 cables, not interchangeable
max. 200 m (maximum capacity of cables 60nF)
1,5 mm
2
Connection with 2 cables, not interchangeable
max. 150 m
max. 300 m (maximum capacity of cables 60nF)
0,5 mm
2
13
0,5
0,75
1,0
40
60
80
7105700.03 - 1/-10/11
1,5
120