REGLAGE DES POINTS DE CONSIGNE
SET COMP#1 SPs (1)
Demand Limit=OFF
Minimum Amps=040%
Maximum Amps=100%
SET COMP SPs (2)
StageMode =Normal
StageSequence# = 01
Max Compr ON = 01
SET COMP SPs (3)
o
StageDeltaT = 1.0
F
Stop-Start = 03 min
Start-Start = 40 min
SET COMP SPs (4)
Full Load = 300 sec Name
Plate RLA 085
SET COMP SPs (5)
Nom Capacity = 0100T
HotGasBypass = 30%
SET COMP SPs (6)
InterLokTmr= 010sec
UnloadTimer = 030 sec
SET COMP SPs (7)
EWWD Automatic
Vane Control
(page vierge)
SET COMP SPs (8)
MAX KW = 76.0
Lag Start = 000Sec
Step Down = 060Sec
SET COMP SPs (9)
Protocol =M-BUS MSTR
Ident Number= 001
Baud Rate = 19200
SET COMP SPs (10)
Refrg Sat Pressure
Evp Offset =+00.0 psi
Cnd Offset = +00.0psi
SET COMP SPs (11)
o
ELWT Offset = +0.0
F
D - EOMWC00905-10FR - 88/104
SET ALARM LMTs (1)
SET PASSWORD
LowEvPrHold=33psi
Enter
LowEvPrUnld=31psi
Password:00000
LowEvPrStop=29psi
No Access Given
SET ALARM LMTs (2)
SET PASSWORD (2)
HighCondPr =140psi
Tech Password
o
HiDschT-Load=170
F
00000 00000
o
HiDschT-Stop=190
F
No Access Given
SET ALARM LMTs (3)
EWWD Compressor
Oilless Design
(page vierge)
SET ALARM LMTs (4)
o
Surge Slp Str=20
F
o
Surge Tmp Run=06
F
MtrCurThrshld=10%
SET ALARM LMTs (5)
Evap Freeze= 34.0° F
Cond Freeze= 34.0°F