SET COMP#N (10)
Refrg Sat Pressure
Evp Offset=+00.0psi
Cnd Offset=+00.0psi
SET COMP#N (11)
ELWT Offset=+00.0°F
Réglage des limites d'alarme
SET ALARM LMTS (1)
LowEvPrHold=33psi
LowEvPrUnld=31psi
LowEvPrStop=29psi
SET ALARM LMTS (2)
HighCondPr = 140psi
HiDschT-Load=170
HiDschT-Stop=190
SET ALARM LMTS (3)
EWWD Compressor
Oilless Design
(page vierge)
SET ALARM LMTS (4)
Surge Slp Str=20
Surge Tmp Run=12
MtrCurrThrshld=05%
Seuls des techniciens de compresseur qualifiés doivent régler ces points de consigne.
SET ALARM LMTS (5)
Evap Freeze=34.0
Cond Freeze=34.0
Réglage des points de consigne de la tour
SET TOWER SPs (1)
TowerControl = None
Tower Stages = 2
StageUP/DN=080/020%
D - EOMWC00905-10FR - 80/104
°