Terminal No.
Function
1-2
Power supply
3
GND
4-5
Aerial
8-9
24Vac
SCA o
10-11
Service light
12-13
PHOTO TEST
14
COM
15
OPEN
16
CLOSE
17
Step-by-Step
18
PED
19
COM
20
STOP
21
PHOT O
22
SWO
23
SWC
24
PHOT C
25-26
DAS
27-28-29
Motor
27-30
Capacitor
31-32
Blinker
1) Cut-off power supply.
2) Manually release the wing, move it to approx. half-stroke and lock it again.
3) Reset power supply.
4) Send a step-by-step control signal by pressing the button or the remote control key.
5) The door/gate should move in the opening phase. Conversely, use the MINV logics to invert the opening direction.
6) Cut-off and restore power supply.
CP.GLISS.RI - CP.GLISS2000.O.MC - MATRIX
CONTROL UNIT
INPUT/OUTPUT FUNCTIONS
Description
Input, 230Vac 50Hz (1-Phase/2-Neutral)
Ground connection. Use the connector preset on the fitting plate of the control unit.
Earthing is COMPULSORY, through this connection also the metal structure of motoriza-
tion are grounded.
Connection of the insertable radio receiver card (4-signal/5-display).
Output, power supply of accessories, 24VAC/1A max
Normally Open clean contact, configurable as SCA (open gate light), timed service light (see
SERL Logic) or as second radio channel (see Logics 2 Ch).
N.O. free contact. It is used to power photocell transmitters in TEST operating mode.
See diagram Fig.3 and TST1 and TST2 Logic.
Common for control inputs.
Input, push-button for OPEN contact (Normally Open contact) Contact usable for timed open-
ings through timer.
Input, CLOSE push-button (N.O. contact)
Input, step-by-step push-button (N.O. contact)
Input, pedestrian push-button (N.O. contact). It controls the partial opening. Configuration is
through parameter TPED. When TCA time has elapsed (if activated) a closure control signal is
sent.
Common, for limit switches and safety devices
Input, STOP push-button (N.C. contact)
Input, (N.C. contact) for safety devices (e.g. photocells).
In the closing phase: the contact opening causes the motor stop. Common: when the photocell
is released, the motor inverts the movement direction (open).
In the opening phase: the contact opening causes the motor stop. When the photocell is re-
leased, the motor re-starts the opening operation.
Input, OPEN limit switch (N.C. contact)
Input, CLOSE limit switch (N.C. contact)
Input (N.C. contact) for safety devices (e.g. photocells).
In the closing phase: Configuration through PHCL Logic.
In the opening phase: Configuration through PHC Logic.
Input, safety edge
Resistive edge: "DAS" Jumper closed
Mechanical edge: "DAS" Jumper open
When the edge is activated, the gate movement is stopped and reversed for about 3s.
If the edge is not in use: "DAS" Jumper open, 25-26 terminals are short-circuited.
Connection of motor 230Vac - single-phase:
27-Phase/28-Common/29-Phase
Connection of capacitor
Connection of blinker, 230Vac 40W max.
To check connections:
13