Cable connection
060G1034
14 = black
15 = brown
16 = blue
Tilslutninger
Nødvendige tilslutninger
Klemme:
25-26 
Forsyningsspænding 24 V a.c.
18-19 
Pt 1000 føler ved gaskølerafgang (S GC 2 )
14,15,16 Tryktransmitter type AKS 2050, -1 til 159 bar 
For at registrere det korrekte tryk skal den monteres så 
tæt ved gaskøleren som muligt.
5-6 
Spændingsudgang til styring af ICMTS ventil.
Applicationbestemte tilslutninger
Klemme:
1-2 
DI-indgang til enten:
• Ekstern hovedafbryder (se o02 og r12)
ELLER 
Kontaktfunktion til hævning af kapaciteten (optimeret 
COP-drift stoppes)  (se o02). 
Åben forbindelse = optimeret COP-drift
Sluttet forbindelse = extra kapacitet.
12-13   Alarmrelæet
Der er forbindelse imellem 12 og 13 i alarmsituationer.
14,16,17  Optional. Der kan tilsluttes en tryktransmitter, så trykket 
i receiveren kan følges. Tryktransmitteren skal være en 
AKS 2050, -1 til 59 bar. 
21-24  Hvis trykket i receiveren skal reguleres, skal der tilsluttes 
en ventil type CCM eller ETS.
18-20  Varmegenvinding. Et spændingssignal på 2-10 V vil hæve 
gastryksreferencen.
3-4  
Datakommunikation
Monteres kun, hvis der også er monteret et datakommuni-
kationsmodul. 
Det er vigtigt, at installationen af datakommunikations-
kablet udføres korrekt. 
Se separat litteratur nr. RC8AC...
Vigtigt
PGC og SGC2 skal monteres tæt ved gaskølerens afgang for at give
korrekt signal.
2 
0 V =  
10 V =  
<-------max. 5 m ---------------->
DANSK
Instructions  RI8NG552  ©  Danfoss  10/2011 
ventil lukket, 
Valve closed, 
ventil åben 
Valve open 
8 VA
AKS 11: Max. 100°C
AKS 21: Max. 180°C
Connections
Necessary connections
Terminals:
25-26  Supply voltage 24 V a.c.
18-19  Pt 1000 sensor at gas cooler outlet (S GC 2 )
14,15,16 Pressure transmitter AKS 2050, -1 to 159 bar
To register the correct pressure it must be mounted as    
close as possible to the gas cooler.
5-6 
Voltage output to control the ICMTS valve.
Application dependent connections
Terminals:
1-2 
DI-input to either:
• External main switch (see o02 and r12)
OR
Contact function for increasing capacity (optimised COP 
operation stopped). (see o02) 
Open connection = optimised COP operation
Closed connection = extra capacity.
12-13   Alarm relay
There is connection between 12 and 13 in alarm situa  t ions 
14,16,17 Optional. A pressure transmitter can be connected so 
that the pressure in the receiver can be monitored. The 
pressure transmitter must be an AKS 2050, -1 to 59 bar.
21-24  If receiver pressure is to be controlled, a CCM or ETS valve 
should be connected.
18-20  Heat recovery. A voltage signal between 2 and 10 V will 
increase the gas pressure reference.
3-4  
Data communication
Mount only, if a data communication module has been 
mounted.
It is important that the installation of the data communi-
cation cable be done correctly. Cf. separate literature No. 
RC8AC...
Important
PGC and SGC2 must be mounted near the gas cooler outlet to produce
a correct signal.
Ventil geschlossen, 
 Vanne fermée
Ventil offen 
  
Vanne ouverte
High pressure valve
Vhp
Gas bypass valve
Vgbp
L > 5 m => AKA 211. Se manual
L > 5 m => AKA 211. See manual
L > 5 m => AKA 211. Siehe Manual
L > 5 m => AKA 211. Voir manual
ENGLISH
   EKC 326A