MONITOR 3
LINE
EXAMPLE
(1)
N.CYCLE=
(2)
C1ID=1PB ST_01.0001
(3)
Vbif=1.68V/el = 40.4V
(4)
Vbef=1.81V/el = 43.4V
(5)
Ibif= 36A Ibef= 35A
(6)
Tf =0h13m Tef=0h13m
(7)
Ahf= 7 AhEf= 7
(8)
-- Message
GUARANTEE
The machine is guaranteed 12 months from the date of installation.
The guarantee covers parts found to be defective in manufacturing or assembly.
The guarantee does NOT cover damage caused by incorrect usage and/or installation.
The guarantee lapses if any tampering is discovered.
For any problems, please refer to an AUTHORISED RETAILER or directly to S.P.E. Elettronica Industriale
D00241-03
DESCRIPTION
Number of charge cycle and current charge phase
7 – Ph 1
E.g. : charge cycle 5 and Phase 3
Charging curve unique identification
Battery voltage at start of phase (Vbif) expressed first as element
voltage (V/el), then as absolute voltage (V)
Battery voltage at end of phase (current) (Vbef) expressed first
as element voltage (V/el), then as absolute voltage (V)
Current at start of phase (Ibif) and current at end of phase (Ibef)
Single phase time (Tf) and Overall charge time at end of phase
(Tef)
Ah supplied in the selected phase (Ahf) and overall charge Ah
(AhEf)
Indicates any faults occurring during the charge cycle