Parameters Menu - Transparent Parameters
31 parameters are available, indicated by the letter "P", which are not modifiable from Remote Timer Control.
Table 7- Parameters - Transparent
Parameter
P01
Ignition power
P02
Heating ramp
P03
Virtual setpoint min. temperature
P04
Heating standby time
P05
Heating Post-Circulation
P06
Pump operation
P07
Modulating pump min. speed
P08
Modulating pump start speed
P09
Modulating pump max. speed
P10
Pump deactivation temperature during Post-Circulation
P11
Pump activation hysteresis temperature during Post-Circulation
P12
Heating user min. setpoint
P13
Heating user max. setpoint
P14
Max. output in heating
P15
DHW ramp
P16
DHW standby time
P17
DHW pump Post-Circulation
With B02 = 7 - Not implemented
P18
With B02 = 8 - DHW user min. setpoint
With B02 = 9 - DHW user min. setpoint
With B02 = 7 - Not implemented
P19
With B02 = 8 - DHW user max. setpoint
With B02 = 9 - DHW user max. setpoint
P20
Max. output in DHW
With B02 = 7 - Not implemented
P21
With B02 = 8 - Hot water tank hysteresis
With B02 = 9 - Hot water tank hysteresis
With B02 = 7 - Not implemented
P22
With B02 = 8 - Primary setpoint
With B02 = 9 - Primary setpoint
With B02 = 7 - Not implemented
P23
With B02 = 8 - Legionella protection
With B02 = 9 - Legionella protection
P24
Fan frequency in standby mode
P25
Modulating pump adjustment temperature
P26
Primary exchanger protection temperature
P27
System min. pressure value
P28
System nominal pressure value
P29
Exchanger protection intervention
P30
Heating hysteresis after ignition
P31
Timer for heating hysteresis after ignition
Notes
1.Parameters with more than one description vary their function and/or range in relation to the setting of the parameter
given in brackets.
2.Parameters with more than one description are reset to the default value if the parameter given in brackets is modified.
3.The Maximum Heating Power parameter can also be modified in Test Mode.
176
Description
cod. 3541T264 - Rev. 00 - 11/2021
Range
70
0-100%
30
1-10°C/minute
1
20-80°C
20
0-10 minutes
4
0-255 minutes
3
0-3 Operation strategy
0
0-100%
30
0-100%
75
30-100%
100
0-100°C
35
0-20°C
5
10 ÷ 80°C
20
20 ÷ 80°C
80
0-100%
80
1-10°C/min
5
0-255 seconds
120
0-255 seconds
30
--
--
10° ÷ 40°
10°
10° ÷ 40°
10°
--
--
40° ÷ 70°
65°
40° ÷ 70°
65°
0-100%
80%
--
--
0° ÷ 60°
0° ÷ 60°
--
--
70° ÷ 85°
80°
70° ÷ 85°
80°
--
--
ON - OFF
OFF
ON - OFF
OFF
0-255 Hz
0
0-60°C
20
0-80°C
35
--
--
--
--
0 = No F43,
0
1-15 = 1-15°C/second
6-30°C
10
0-180 seconds
60
CLOVER
125
160
220
320
30
50
45
30
1
1
1
1
20
20
20
20
4
4
4
4
3
3
3
3
0
0
0
0
30
30
30
30
75
75
75
75
100
100
100
100
35
35
35
35
5
5
5
5
20
20
20
20
80
80
80
80
80
80
80
80
5
5
5
5
120
120
120
120
30
30
30
30
--
--
--
--
10°
10°
10°
10°
10°
10°
10°
10°
--
--
--
--
65°
65°
65°
65°
65°
65°
65°
65°
80%
80%
80%
80%
--
--
--
--
--
--
--
--
80°
80°
80°
80°
80°
80°
80°
80°
--
--
--
--
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
0
0
0
0
20
20
20
20
35
35
35
35
--
--
--
--
--
--
0
0
0
0
10
10
10
10
60
60
60
60