FlameGard 5 Test Lamp
Quick Start Guide
When the Flame Detector senses the Test Lamp, the red LED will
blink slowly. The green light may also blink. After a time delay the
red LED will start to blink quickly. This signifies the completion of the
test.
The FlameGard 5 Test Lamp triggers a Flame Detector into alarm. The
system must be disabled during test if you do not want false trips.
To conserve charge, do not operate the test lamp longer than is necessary
to test a Flame Detector.
When the battery level drops below the level required to maintain the proper
intensity of the lamp, an internal low voltage circuit will shut the lamp off until
the battery has been recharged. Please refer to Operating Manual for
complete recharging instructions.
It is mandatory that the FlameGard 5 Test Lamp be kept on charge when not
in use to prevent excessive battery discharge. The batteries may be charged
an average of 500 times before the battery pack is replaced.
Please refer for maximum distance to each detector.
Detector Test Mode Initiation or/Detector Alarm Trigger with FlameGard
5 Test Lamp
Flame Detector to
Test
FlameGard UV-IR
FlameGard 5 UV/IR-E
FlameGard 5 MS-IR
FlameGard 5 MS
FlameGard 5 MS
GB
Maximum Distance
to Detector (m)
6
6
11 (High Sensitivity)
6 (Medium Sensitivity)
2.5
(Low Sensitivity)
Results
Trigger into alarm mode
Trigger into alarm mode
Enter test mode
Enter test mode
Enter test mode
MAN5TL-QG/01