SPLIT-TYPE AIR CONDITIONERS
INSTALLATION MANUAL
1. BEFORE INSTALLATION
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
• Be sure to read these safety precautions and instructions.
• After reading this manual, be sure to store it with the OPERATING INSTRUCTIONS for future reference.
• Please report to your supply authority or obtain their consent before connecting this equipment to the power supply system.
■ Do not install the unit by yourself (user).
whom you purchased the unit.
■ Follow the instructions detailed in the installation manual.
ing, or leakage of water.
■ When installing the unit, use appropriate protective equipment and tools for
safety.
Failure to do so could cause injury.
■ Install the unit securely in a place that can bear the weight of the unit.
If the installation location cannot bear the weight of the unit, the unit could fall
causing injury.
■ Do not alter the unit.
■ Perform electrical work according to the installation manual and be sure to use
an exclusive circuit. Do not connect other electrical appliances to the circuit.
■ Ground the unit correctly.
Do not connect the ground wire to a gas pipe, water pipe, lightning rod or
telephone ground. Defective grounding could cause electric shock.
If required, take measures against leakage current.
■ Do not damage the wires.
■ Be sure to shut off the main power when setting up the indoor P.C. board or
wiring.
Failure to do so could cause electric shock.
If gas leaks and accumulates around the unit, it could cause an explosion.
■ Do not use intermediate connection of the power cord or the extension cord.
Do not connect many devices to one AC outlet.
an electric shock, the unit falling, etc.
■ When plugging the power supply plug into the outlet, make sure that there is
no dust, blockage, or loose parts both in the outlet and on the plug. Verify that
the power supply plug is completely in the outlet.
If there is dust, blockage, or loose parts on the power supply plug or the outlet, it could
■ Please follow applicable federal, state, or local codes to prevent potential
leakage/electric shock. Or install a ground fault interrupt for the prevention of
leakage and electric shock.
■ Perform the drainage/piping work securely according to the installation manual.
If there is defect in the drainage/piping work, water could drip from the unit, and
damage household items.
JG79J820H01
MSZ-FS06/09/12/15/18NA
When installing multi units, refer to the
installation manual of the multi unit for
outdoor unit installation.
WARNING
-
-
CAUTION
Required Tools for Installation
Phillips screwdriver
Level
Scale
Utility knife or scissors
3 in. (75 mm) hole saw
Torque wrench
Wrench (or spanner)
(Could lead to death or serious injury.)
■ Securely attach the electrical cover to the indoor unit and the service panel to
the outdoor unit.
If the electrical cover of the indoor unit and/or the service panel of the outdoor unit are
an electric shock.
■ When installing, relocating, or servicing the unit, make sure that no substance
Any presence of foreign substance such as air can cause abnormal pressure rise
and may result in explosion or injury. The use of any refrigerant other than that
breakdown. In the worst case, this could lead to a serious impediment to securing
product safety.
■ Do not discharge the refrigerant into the atmosphere. Check that the refriger-
ant gas does not leak after installation has been completed. If refrigerant leaks
during installation, ventilate the room.
heater, space heater, stove, etc., harmful gases will be generated.
■ Use appropriate tools and piping materials for installation.
The pressure of R410A is 1.6 times higher than R22. Not using the appropriate
tools and materials, or improper installation could cause the pipes to burst causing
an injury.
■ When pumping down the refrigerant, stop the compressor before disconnecting
the refrigerant pipes.
If the refrigerant pipes are disconnected while the compressor is running and the
stop valve is open, air could be drawn in and the pressure in the refrigeration cycle
could become abnormally high, causing the pipes to burst.
■ When installing the unit, securely connect the refrigerant pipes before starting
the compressor.
If the compressor is started before the refrigerant pipes are connected and the
stop valve is open, air could be drawn in and the pressure in the refrigeration cycle
could become abnormally high, causing the pipes to burst.
■ Install the unit according to national wiring regulations.
■ When opening or closing the valve below freezing temperatures, refrigerant may
spurt out from the gap between the valve stem and the valve body, resulting in
injuries.
(Could lead to serious injury when operated incorrectly.)
This could cause injury.
■ Do not install the outdoor unit where small animals may live.
If small animals enter the unit and damage its electrical parts, it could cause a
5/32 in. (4 mm) hexagonal
wrench
Flare tool for R410A
Gauge manifold for R410A
Vacuum pump for R410A
Charge hose for R410A
Pipe cutter with reamer

Publicité

loading

Sommaire des Matières pour Mitsubishi Electric MSZ-FS06NA

  • Page 1 Required Tools for Installation JG79J820H01 Phillips screwdriver 5/32 in. (4 mm) hexagonal MSZ-FS06/09/12/15/18NA Level wrench Scale Flare tool for R410A Utility knife or scissors Gauge manifold for R410A When installing multi units, refer to the 3 in. (75 mm) hole saw Vacuum pump for R410A SPLIT-TYPE AIR CONDITIONERS installation manual of the multi unit for...
  • Page 2 1-3. SPECIFICATIONS 1-3-1. POWER SUPPLY AND INDOOR/OUTDOOR WIRE CONNECTION MSZ-FS06NA MSZ-FS15NA • Power should be taken from an exclusive branched circuit. MODEL MSZ-FS09NA MSZ-FS18NA •...
  • Page 3 1-4. INSTALLATION DIAGRAM Use the wall hole sleeve (C) to prevent indoor/outdoor connecting wire (A) from ACCESSORIES contacting metal parts in the wall and to Check the following parts before installation. protect the wiring from rodents. <Indoor unit> Wall hole cover (D) Indoor unit Installation plate Seal the wall hole...
  • Page 4 2. INDOOR UNIT INSTALLATION 2-1. ATTACHING THE INSTALLATION PLATE Ceiling 3-3/8 in. (85 mm) or more 5-11/16 in. (143 mm) or more for left/ left rear piping (using spacer) • To prevent installation plate (1) from vibrating, be sure to install the attachment screws in Installation plate (1) Level the holes indicated in the illustration.
  • Page 5 2-4. PIPE FORMING AND DRAIN PIPING 2-4-1. PIPE FORMING • Place the drain hose below the refrigerant piping. Felt tape (4) • Make sure that the drain hose is not crowded or bent. Piping tape (G) • Do not pull the hose when applying the tape. •...
  • Page 6 3. OUTDOOR UNIT INSTALLATION 3-1. CONNECTING WIRES FOR OUTDOOR UNIT 1) Remove the service panel. 2) Remove the conduit cover. 3) Attach the conduit connectors to the conduit plate with lock nuts then secure it against unit with screws. 4) Connect the ground wires of indoor/outdoor unit connecting wire (A) and power supply cord (K) 19/32 in.
  • Page 7 3-3. PIPE CONNECTION • Be sure to wrap insulation around the piping. Direct contact with the bare piping may result in burns or frostbite. Indoor unit connection Connect both liquid and gas pipings to indoor unit. frigeration oil on screw threads. Excessive tightening torque will result in damage on the screw.
  • Page 8 5. RELOCATION AND MAINTENANCE 5-1. REMOVING AND INSTALLING THE PANEL ASSEMBLY Removal procedure 1) Unlock the upper and lower vanes as shown in using a thin instrument. Then, remove the horizontal vanes. 2) Remove the front panel. 4) The panel assembly consists of 3 components. Remove them in the following order: Unlock right, left, and center bottom.
  • Page 9 Outils nécessaires à l’installation JG79J820H02 Tournevis Phillips Niveau Outil d’évasement pour le modèle R410A Règle graduée Collecteur à jauge pour le modèle R410A Lors de l’installation de plusieurs unités, Pompe à vide pour le modèle reportez-vous au manuel d’installation Scie-cloche de 3 in. (75 mm) R410A CLIMATISEURS A ELEMENTS SEPARES correspondant pour l’installation de l’unité...
  • Page 10 1-2. CHOIX DE L’EMPLACEMENT D’INSTALLATION UNITE INTERNE Remarque : Remarque : • Emplacement favorisant la circulation d’air. • Emplacement favorisant une bonne répartition de l’air froid télécommande dans des pièces éclairées par des lampes (ou chaud) dans la pièce. • Mur solide sans vibration. un endroit à...
  • Page 11 Utilisez le manchon d’ouverture murale (C) pour éviter ACCESSOIRES ou toute détérioration causée par les rongeurs. <Unité interne> Cache d’ouverture murale (D) Unité Gabarit d’installation Bouchez l’ouverture murale interne avec du mastic (H). Manchon 4 × 25 mm d’ouverture à l’aide d’une bande de murale (C) Bande de feutre (pour la tuyauterie gauche ou arrière gauche)
  • Page 12 2. INSTALLATION DE L’UNITE INTERNE 2-1. FIXATION DU GABARIT D’INSTALLATION Plafond 3-3/8 in. (85 mm) minimum 5-11/16 in. (143 mm) minimum pour la tuyauterie côté gauche/arrière gauche (utiliser une entretoise) Gabarit d’installation (1) Niveau 4-7/8 in. 5-1/4 in. (122,5 mm) (132,5 mm) minimum minimum...
  • Page 13 • Placez le tuyau de vidange sous la conduite de réfrigérant. Bande de feutre (4) • Assurez-vous que le tuyau de vidange n’est ni encombré ni plié. Ruban adhésif de tuyauterie (G) • Ne tirez pas sur le tuyau pour y appliquer le ruban adhésif. Tuyau de liquide •...
  • Page 14 3. INSTALLATION DE L’UNITE EXTERNE 3-1. RACCORDEMENT DES CABLES DE L’UNITE EXTERNE 1) Retirez le panneau de service. 2) Déposez le cache de conduit. sur l’unité avec des vis. 19/32 in. (15 mm) L1 L2 d’alimentation (K) au support TB. Cordon d’alimentation (K) Fil conducteur du bloc de raccordement.
  • Page 15 reporter à la section 3-2). • S’il est trop serré, il risque de se rompre et de provoquer une fuite de réfrigérant. • Assurez-vous que la tuyauterie est enveloppée d’isolant. Un contact direct avec la tuyauterie nue peut entraîner des brûlures ou des engelures. Raccordement de l’unité...
  • Page 16 5. DEPLACEMENT ET ENTRETIEN 5-1. DEPOSE ET INSTALLATION DU PANNEAU Dépose à 2) Déposer le panneau frontal. Déver- 4) L’ensemble du panneau se compose de 3 composants. Retirez-les dans l’ordre suivant: rouiller droite, gauche, et centre bas. Pour retirer le composant droit, tirer sur le coin supérieur droit.