Switching State; Electrical Connection - Fema DCM Série Mode D'emploi

Masquer les pouces Voir aussi pour DCM Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.
Pressure limiters with mechanical interlock of the

switching state

Maximum pressure limiter ABC...-205
Minimum pressure limiter ABC...-206
Instead of the microswitch with automatic reset, a "bistable" microswitch is
installed in the limiters.
When the pressure reaches the value set on the scale, the microswitch
switches over and remains in this position. The catch can be relased by
pressing in the unlocking button (marked on the scale side of the switching
device by a red dot). The limiter can not be unlocked until the pressure has
decreased by a certain amount or, in the case of interlocking at the lower switching point, is
increased again. According to version, the interlock can be effective for a rising value
ABC ...-205 or for a falling value ABC...206.
3.1
Technical data as for 1.1
3.2

Electrical connection

3.2.1 Maximum pressure limiting
Switching over and interlocking on rising temperature.
Additional function (...205). Connection of control circuit to terminal 1 and 3.
3.2.2 Minimum pressure limiting
Switching over and interlocking on falling temperature.
Additional function (...206).
Connection of control circuit to terminal 2 and 3.
ABC...-205
ABC...-206
30