Mounting and securing
Mark out and drill fixing holes (A) for smoke switch control unit using fitting template or cut M5 thread if
X
X
necessary.
Drill additional hole (B) for 230V power supply.
X
X
Make opening for additional connections (C).
X
X
IMPORTANT:
To guarantee correct functioning of the smoke switch, GEZE recommends that the distance between the upper
edge RSZ 6 and the ceiling be at least 10 mm!
The smoke detector can only be mounted to the vertical wall above the door opening. Observe assembly area
(Fig.: 6.1.1)
Depending on the hold-open device, please observe the document "Instructions for Installation, Commissioning,
Operation and Maintenance of the GEZE Hold-Open Device FA GC" as well.
6.3
Fixing smoke switch control unit and mains connection
DANGER!
Hazard of electric shock!
Electric wiring must only be carried out by professional electricians.
Operating voltage: 230 V AC +10 % / –15 %,
Interrupt power supply.
X
X
Fuse the on-site mains connection with a B10 fuse.
X
X
The GEZE hold-open devices FA GC are appliances of the protection class II
rooms. Ambient temperature -5 °C to 50 °C.
The 230 V supply line is double insulated (with cable jacket), to be inserted at least 8 mm into the terminal area.
Appliances of the protection class II are connected with a two-core cable NYM-O, 2 x 1.5.
The connection can also be done with a three-core cable NYM-J 3 x 1.5. The earth conductor must not be con-
nected then and should be isolated permanently (e.g. additional insulating screw joint or shrink tubing).
Fig.: 6.2.1
Route 230 V mains cable and cable for additional connections into the terminal area (1.).
X
X
Align smoke switch control unit and screw it firmly (2.).
X
X
GB 4
Protection class IP 20, only for dry
RSZ 6