9. Install discharge piping from the condensate discharge port, including a vertical union,
dirt/scale collection piping, piping blowdown valve (C) and horizontal piping with steam, air or
drain trap and an inlet valve (D) for the trap. (See the "Typical Piping Flow" diagram in the "For
Longer Filter Life" section on page 7)
10. Make sure to install a free float trap that discharges condensate continuously during operation
along with separator filter.
Example
SF1 Connection Size
mm
(in)
15 - 40mm
(
-1
1
/
2
50mm
(2)
NOTE: At start-up, large amounts of initial condensate are generated. Also, during batch
operation, a large amount of condensate may accumulate in the piping when
operation stops. If there are concerns that a large amount of condensate could flow
into the separator filter, make sure to install a piping blowdown valve at the inlet of
the separator filter to ensure that the condensate is eliminated, or install a steam
trap with sufficient discharge capacity even when the pressure differential is
extremely low. (See "For Longer Filter Life" items 1, 2 and 3)
11. Close the dirt/scale blowdown valve (E) below the dirt/scale collection piping, open the
separator filter inlet valve (A), outlet valve (B) and the trap inlet valve (D), and ensure that the
separator filter functions properly. (See the "Typical Piping Flow" diagram in the "For Longer
Filter Life" section on page 7)
12. After letting some live steam/air enter the filter, allow the separator filter to cool to ambient
temperature, and then tighten the clamp further.
13. Ensure the maintenance space is sufficient for maintenance (i.e. replacement of internal filter).
If there is a problem, determine the cause using the "Troubleshooting" section of this manual.
For Steam Use
1
/
)
SS1 Series, J3S-X, J3X
2
JH5SL, J5S-X, J5X
SF1 Connection Size
mm
15, 20
JA3, JA3D, SS1VG Series
JA5, JAH5RG Series
(in)
(
/
-
/
)
1
3
2
4
(1)
25
1
/
(1
)
40
2
(2)
50
For Air Use
Min. Maintenance Space (S)
mm
(in)
(4)
100
(6)
150
(12)
300
(14)
350

Publicité

Table des Matières
loading