1

Safety information

Before putting the unit into operation, the safety information, the instructions for installation
and the operating manual that is supplied with the unit must be read and observed.
Please read the safety information carefully and comply with the items stated. This is a matter of safety
for personnel and equipment. The unit is predominantly designed as a temperature controller for
electrical heating systems. Improper application, installation, configuration or operation of a system or
that which goes against the machine's intended purpose may cause severe personal injuries and
extensive property damage!
Important: This unit is not a safety temperature limiter according to DIN EN 60730-1
The unit must not be installed in potentially explosive atmospheres. If a process function originating
from an explosion-risk area is to be processed by the unit installed outside the explosion-risk area, all
supply lines of the unit leading into the explosion-risk area must be guided via safety barriers!
The prerequisite for error-free and safe operation of the unit is its careful transport and storage, as
well as correct assembly and installation. This device may only be installed, configured, parameter-
ized and commissioned by qualified persons who are familiar with installation, commissioning and
maintenance of comparable devices and with the system in which the device will be applied and who
have appropriate knowledge in the field of instrumentation and control. Operating staff of the system
in which the device is to be used must be instructed on operation and control of the unit by qualified
persons.
Please observe and comply with:
The contents of the present manual for installation and operation of the unit, in particular
the information on installation, taking into operation, any notes in bold print and adjustment of
the device to suit the overall system.
Any and all safety information attached to the unit
Any and all relevant safety regulations for installation and operation of electrical systems
The keeping of this manual in a safe place for future use
The regulations stated in the present manual are applicable and valid in all EU countries. For use of
the device outside an EU country, the relevant national rules and regulations must be considered.
This device has been produced and tested in accordance with DIN EN 61010 Part 1, "Safety
requirements for electrical equipment for measurement", and has left our company in an error-free
condition in terms of its safety and functionality.
1.1

Place of application of the unit

The unit is designed as a temperature controller for flexible applications in electrical heating systems.
The place of operation or installation of the temperature controller must not be close to motors,
transformers, circuit breakers or other inductive loads. It must be shock-free and vibration-free and
positioned on solid ground. The ambient temperature at the place of installation must be between -20°
C and 45°C, with a relative humidity of 90% (noncondensing). Aggressive and corrosive gases and
vapors may damage the unit.
®
© BriskHeat
Corporation
®
. All rights reserved.
3
BH-330 Inline Controller Operation Manual
2

Instructions for installation

Please read the installation instructions carefully and comply with all conditions mentioned here during
installation of the unit. In case of non-compliance with the Instructions for installation, faults or malfunc-
tions may occur, or the unit may fail to comply with the required EMC guidelines and the conditions for
CE-conformity will not be fulfilled.
Before connection of the unit and before putting it into operation, please ensure that the operating
voltage and the conditions for the operating voltage required by the unit correspond to the conditions on
site (cf. name plate and technical specifications). If required, take any appropriate measures.
The output connector on the controller is a PE+6, 7-pole socket with the configuration shown below.
Wire the heating element and sensing device to the plug included matching the function to the pin
numbers below. Sensing devices must match the type indicated by the controller part number. See
page 2.
Pin
Function
1
L Heater
2
N Heater
3
Not connected
4
Not connected
5
Sensor +
6
Sensor -
PE
Earth ground
Please make sure that the load voltage on site is switched off and secured against accidental reactiva-
tion during installation of the device. The electrical connections must be made on the basis of the con-
nection diagram and the relevant national rules and regulations. The supply lines for the device must be
laid such that they are free from any tensile loads and are not exposed to risks of shearing or crushing
under any circumstances. Mounting accessories are available as listed on page 2. The controller along
with the input and output connections are sealed and rated as IP67. Proper assembly of the IP67 rated
plug is the responsibility of the customer.
Incorrect wiring or connection of the unit may cause severe damage of the unit and connected devices.
The present manual does not contain all notes for regulations, standards, etc. that must be
observed and complied with during working with the unit in connection with systems and plants. Any
such regulations, standards, etc. shall be complied with and observed by the operator of the unit with
regard to specific requirements of the respective system or plant.
3

Start-up and adjustment of controller

This unit requires the use of a BH-310 Infrared Remote Control Programming Unit for operation. Do not
plug the unit into power until the remote is ready for operation. See the BH-310 Infrared Remote Con-
trol Programming Unit manual for further information.
Plug the power input connection into an appropriate power source. Hold the BH-310 a minimum of
approximately 0.5 to 0.7 meters from the controller and align the infrared sensor with the sensor on the
controller. When the units are linked, you will see the Set (set-point) and the Value (current) tempera-
tures displayed on the remote screen. The LED on the controller will alternate while and another color
when linked.
®