Avoid static and dynamic overpressure exceeding the given over-
load pressure.
Even if the bursting pressure is exceeded only for a short time
the unit can be destroyed (danger of injuries)!
Indication of the current system pressure as from 5% of the
value of the measuring range. "All LEDs OUT" does not mean
that the system is free of pressure!
The unit
• can be used as N.O. or N.C.
• and operates with the hysteresis function.
When the system pressure is
rising, the output switches when
the switch-on point has been
reached (S); when the system
pressure is falling again, the out-
put switches back when the
switch-off point (R) has been
reached.
The hysteresis can be set: First
the switch-on point is set, then
the switch-off point with the
requested difference.
Setting range:
Order no.
PB5xx0
PB5xx1
PB5xx2
PB5xx3
PB5xx4
PB5xx6
PB5xx7
Switch-on point
(S)
20 ... 400 bar
12.5 ... 250 bar
5 ... 100 bar
1.25 ... 25 bar
0.5 ... 10 bar
0.125 ... 2.5 bar
0.05 ... 1.0 bar
P
S
R
1
0
1
0
Switch-off point
(R)
12 ... 392 bar
7.5 ... 245 bar
3 ... 98 bar
0.75 ... 24.5 bar
0.3 ... 9.8 bar
0.075 ... 2.45 bar
0.03 ... 0.98 bar
hystereris
t
N.O.
N.C.
in steps of
4 bar
2,5 bar
1 bar
0.25 bar
0.1 bar
0.025 bar
0.01 bar
13