4
Assembly
4.1
Assembly instructions
The assembly of the access sensor is made as shown in Fig. 2.
• Mount the access sensor so that the front with the transmitter and receiver is pointing to the moni-
tored door.
• Stick the enclosed reflective foil on the door and the side wall exactly opposite of the IR sensor.
Note:
The distance between the IR sensor in the access sensor and the reflective foil must not
exceed 10 cm. Please reposition the access sensor accordingly, if necessary.
5
Installation and operation
5.1
Operating and display elements
The operating and display elements are shown in Fig. 3.
Key for Fig. 3
1
Infrared receiver
2
Infrared diode (transmitter)
3
Multi-LED for the status display
4
CAN bus connection
5
CAN bus connection
5.2
Installation
• Connect the access sensor with a CAN bus connection cable to the CMC III PU or to the neighbour-
ing elements on the CAN bus (Fig. 3, Pos. 4, 5).
Display of the status change:
– The two green and the two red CAN bus LEDs on the CAN bus connection flash.
– The multi-LED of the Processing Unit flashes continually in the green – orange – red sequence.
– The multi-LED of the access sensor flashes blue continuously.
• Press the "C" key on the CMC III PU (a first audio signal is issued) and keep it pressed for approx.
3 seconds until a second audio signal is issued.
Display of the status change on the CAN bus LEDs:
– Green LEDs light continuously: CAN bus status "OK".
– Red LEDs light continuously: CAN bus status faulty.
Display of the status change on the multi-LED of the Processing Unit.
– Continuous green light: All units attached to the CAN bus have the "OK" status.
– Continuous orange light: At least one unit attached to the CAN bus has the "warning" status.
– Continuous red light: At least one unit attached to the CAN bus has the "alarm" status.
Display of the status change on the multi-LED of the access sensor:
– Continuous blue flashing: Communication over the CAN bus.
– Green flashing: When the measured value changes or, at the latest, every 5 seconds.
– Continuous red flashing: The access sensor has the "open" status.
– Continuous red light: Invalid measured value.
If the installation is not successful: see Section 1.1.
Rittal CMC III Infrared Access Sensor
Assembly, Installation and operation
EN
6