CRA- 72 and CRA-96 CONTROL PANEL
PR Out : If you press SET button 0,5 sec you can enter MENU. Firstly you will see Pr Out. When you see
PR OUT, if you press SET again you will exit from setup. If you want to see other options you should push
UP or DOWN button.
P1 : P1 sets stabiliser's output voltage. Push the SET button to change the value, the value starts
blinking. Use UP and DOWN buttons to set desired value then push the SET button to save.
Factory setting : 230 Volt Setting Range : 170 V—250 V
P2 : P2 sets the output maximum voltage tolerance. Push the SET button to change the value, the value
starts blinking. Use UP and DOWN buttons to set desired value then push the SET button to save.
Factory setting value : 234 Volt Setting range : P1 value + 10 Volt
P3 : P3 sets the output minimum voltage tolerance. Push the SET button to change the value, the value starts blinking. Use UP and DOWN
buttons to set desired value then push the SET button to save.
Factory setting value : 226 Volt Setting range : P1 value - 10 Volt
P4 : P4 sets output voltage maximum value. When Output voltage value pass this value the output is cut off after the time defined at P6.
Push the SET button to change the value, the value starts blinking. Use UP and DOWN buttons to set desired value then push the SET
button to save.
Factory setting value : 250 Volt Setting range : P1 value + 50 Volt
P5 : P5 sets output voltage minimum value. When Output voltage value pass this value the output is cut off after the time defined at P6.
Push the SET button to change the value, the value starts blinking. Use UP and DOWN buttons to set desired value then push the SET
button to save.
Factory setting value : 190 Volt Setting range : P1 value - 50 Volt
P6 : P6 sets the cut off time for output voltage. Push the SET button to change the value, the value starts blinking. Use UP and DOWN
buttons to set desired value then push the SET button to save.
Factory setting value: 5.0 Sec Setting range: 0,1 sec-20,0 sec
P7 : P7 sets the re-work time after cut off. When the input voltage become inside the defined voltage range , the system waits until P7
value then switch on the output. Push the SET button to change the value, the value starts blinking. Use UP and DOWN buttons to set
desired value then push the SET button to save.
Factory setting value : 5.0 Sec Setting range : 0,1 sec - 20,0 sec
P8 : P8 sets the current protection. If this is ON it means current protection is ACTIVE. If this is OFF it means current Protection is INACTIVE
Push the SET button to change the value, the value starts blinking. Use UP and DOWN buttons to set desired value then push the SET
button to save.
Factory setting value : ON Setting choice : ON – OFF
P9 : P9 sets input current protection maximum value. When the input current pass this value current protection become ACTIVE Push the
SET button to change the value, the value starts blinking. Use UP and DOWN buttons to set desired value then push the SET button to save.
Factory setting value : According to Voltage Power Setting range : 5 amp - 999 amp
P10 : P10 sets the current transformer's ratio. Push the SET button to change the value, the value starts blinking. Use UP and DOWN
buttons to set desired value then push the SET button to save.
Factory setting value: According to Voltage Power Setting range : 10-9999
P11: P11 sets the cut off time according to current protection. When the current goes out off limits, system waits until this value then cut
off output. Push the SET button to change the value, the value starts blinking. Use UP and DOWN buttons to set desired value then push
the SET button to save.
Factory setting value : 2,0 sec Setting range : 0,1 sec - 20,0 sec
P12 : P12 sets the re-work time after current protection cut off. When the current become inside the defined current range, the system
waits until P12 value then switch on the output. Push the SET button to change the value, the value starts blinking. Use UP and DOWN
buttons to set desired value then push the SET button to save.
Factory setting value : 2.0 Sec Setting range : 0,1 sec - 20,0 sec
P13: P13 sets current protection mode. If this value stay OTO , system make RESET automatically. If you set a value after the value you
must make reset manually. Push the SET button to change the value, the value starts blinking. Use UP and DOWN buttons to set desired
value then push the SET button to save.
Factory setting value : OTO Setting range : 2 – 10
P14 : P14 sets motor voltage value . This value work with P15 to arrange the motor speed. Push the SET button to change the value, the
value starts blinking. Use UP and DOWN buttons to set desired value then push the SET button to save.
Factory setting value : 5.0 Sec Setting range : 1 sec - 20 sec
P15: P15 sets motor speed. This value work with P14 value. Push the SET button to change the value, the value starts blinking. Use UP and
DOWN buttons to set desired value then push the SET button to save.