Wire connection
REQUIREMENT
Connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
Pass the wires through the bushing of wire connection holes of the Flow Selector unit.
Keep a margin (Approx. 4.0" (100 mm)) on a wire to hang down the electrical control box at servicing.
The low-voltage circuit is provided for the communication wires. (Do not connect the high-voltage circuit)
1
Loosen the cover mounting screws (2 positions) of the electrical control box, and then
remove the cover.
2
Attach the conduit pipe with a lock nut.
3
The cable clamp (accessory) is installed in the underside of the Flow Selector unit.
4
Connect the power supply wire and communication wire to the terminal blocks of the
electrical control box.
5
Tighten screws of the terminal block securely, and fix the wires with cord clamp attached
to the electrical control box. (Do not apply tension to the connecting section of the terminal
block.)
6
Mount the cover of the electrical control box so that it does not pinch the wires.
Connecting power supply wire and communication wires
Terminal on PCB for Communication wiring
Cable clamp
Communication wire
Power supply terminal block
For communication wire, attach the Clamp filter (accessory) as the picture below.
2.0" to 2.4"
Binding band
(50 to 60 mm)
(Accessory)
Attach round
shaped terminal
(locally procured)
Clamp filter
(Accessory)
EN-19
Ground screw
Power supply wire
Lock nut
Conduit pipe
Cable clamp
(Accessory)
Cable clamp
Clamp filter (Accessory)
Hook 2 nails
Communication wire
(locally procured)
1 turn
0.4"
L1 L2
(10)
0.2"
0.4"
(5)
(10)
2.0"
7.1"
1.6"
(50)
(180)
(40)
Ground wire
Power supply wire
Communication wiring
Terminal block for
remote control
wiring of indoor unit
A
A
B
B
Communication wires
(locally procured)
10
(Unit:in (mm))
See the figure on the
left for connecting wires
to the terminal.
Communication wire
Communication wires
FS unit
terminal on PCB
EN