NOTE: For correct operation, if you wish to pilot the filtration pump using an external relay/remote
switch, eliminate condenser C4.
This operation must be carried out by qualified staff, at an assistance centre.
Massaging water jet pump connection
Connect the massaging water jet pump power supply cable to the OUT 2 clamp (N and F).
It is possible to connect a pump with an overall power of 2.0HP. Maximum admissible load of
230V 1.6 KW.
Output protected with a safety fuse. If the fuse blows, a red led will light up in the HYDRO button
on the front synoptic panel.
Level-control solenoid valve connection
Connect the solenoid valve power supply cable to the OUT 3 clamp (N and F).
Output protected with a safety fuse. If the fuse blows, a red led will light up in the level-control
solenoid valve indicator light on the front synoptic panel.
ATTENTION: the output voltage of the OUT3 clamp is 220Vac. To connect the solenoid valve at
24vac use the designated solenoid valve transformer kit TR324 code 100100835
Level probes connection
Use level probes, available separately, code: 108100816
Use the black cable and the blue cable of the level probe. The brown cable is not required.
Connect pump protection level probe (A) to clamps 11 and 12.
Connect level-control probe (B) to clamps 13 and 14.
Connect overflow level probe (C) to clamps 15 and 16.
It is possible to use other level probe models as long as they are normally closed.
If it is necessary to run the device temporarily without level probes, jumper clamps 15 and 16
CODE
F5
F6
F7
F8
F9
[OPERATION AND MAINTENANCE HANDBOOK
Description of protection fuses
FUNCTION
Lighting fuse
Filtration pump fuse
Massaging water jet pump fuse
Level-control solenoid valve fuse
Internal electronic fuse
]
[V-1.16]
FUSE VALUE
250 V - T 3.15 A
250 V - T 16 A
250 V - T 16 A
250 V - T 3.15 A
250 V - T 1 A
AQUA spa
13