After changing the settings, or whenever a new process start is required, the ETO2 can be restarted in this menu.
Restarts operation while retaining all your current settings. The ETO2 goes to the initial status display.
RESTART
OFFSET CALIBRATION
If it is necessary to calibrate the temperature measured by the ETOG sensor, please follow the steps below:
1.
Disconnect the sensor from terminals 11 and 12 (sensor heating) of the ETO2.
2.
Wait a few hours until the sensor has acquired the same temperature as the ground.
3.
Measure the real ground/sensor temperature and compare it with the temperature shown on the ETO2 display.
4.
Program the offset for the sensor concerned to match the difference between the two temperatures (displayed/real).
Adjust the necessary offset using the encoder button. Press OK.
5.
Reconnect the sensor to terminals 11 and 12 of the ETO2.
NOTE: With the ETOG sensor, the temperature shown on the ETO2 display is always the core temperature of the sensor.
FACTORY SETTINGS
SETUP
Application
Sensor 1
Sensor 2
Select scale
Afterrun time, zone 1
Afterrun time, zone 2
Temp. offset, zone 1
Temp. offset, zone 2
Temp. offset ETF
Temp. setpoint, zones 1+2
OFF temp., zones 1+2
Sensor heating, zones 1+2
Moisture control, zones 1+2
Sensitivity, zones 1+2
Min. water temp.
Max. water temp.
18
All ETO2 factory settings can be restored here. Selecting this option deletes all customised settings.
In the event of setup failure in the STARTUP menu, or whenever new hardware is connected, the primary
setup must be changed in the STARTUP menu. Select PASSWORD and turn the encoder button to the
factory code (1202). The controller will then return to the STARTUP menu, see STARTUP.
Select this option and press OK to return to the main menu.
FACTORY SETTINGS
Electric
ETOG
OFF
Celsius
2.00 hours
2.00 hours
0.0°C
/ 0.0°F
0.0°C
/ 0.0°F
0.0°C
/ 0.0°F
3.0°C
/ 37.4°F
OFF
AUTO
ON
NORM
5°C
/ 41°F
55°C
/ 131°F
OWN SETTINGS
© 2013 OJ Electronics A/S
Type ETO2