Parts to install according to EN 12453 standard
COMMAND TYPE
(out of public area*)
Hold-to-run operation
Impulsive - in sight
(e.g. push-button)
impulsive - out of sight
(e.g. remote)
automatic
* a typical example are those doors which do not have access to any public way
A: Hold-to-run operation made by push-button ex: code ACG2013
B: Hold-to-run operation made by key selector ex: code ACG1010
C: Adjustable power of the motor or photocells to respect impact forces as indicated in Annex A
D: Safety strips and/or other additional devices to reduce the probability of contact with the door.
E: Devices installed in such a way that a person can not be touched by the door.
A - ELECTRIC CONNECTION
B - SW1 - MICROSWITHCES FOR THE GEARCASE SETTING
DIP 1 - MOTOR DECELERATION CALIBRATION (ON) (POINT C)
DIP 2 - PROGRAMMING TIMES (ON)
OPERATING MICROSWITCH
DIP 3 - Waiting time before the automatic closing (ON) (max 5 min.)
DIP 4 - Step by step radio receiver (OFF) - automatic (ON)
DIP 5 - Single impulse control (K BUTT) step by step (OFF) - automatic (ON)
DIP 6 - Normal working (OFF) – Park working (ON)
DIP 7 - Encoder exclusion as security (OFF - encoder on / ON - encoder off)
DIP 8 - Function of the key OPENING 2 check in Park mode.
ON - the key OPENING 2 is always authorized,
OFF- the key OPENING 2 is authorized only if there is no presence on INPARK.
DIP 9 - Working after black-out WITH batteries.
ON - The rod opens and stops in the opening position with the exclusion of all
USE OF THE SHUTTER
Skilled persons
Skilled persons
(public area)
A
B
C or E
C or E
C or E
C and D, or E
C and D, or E
C and D, or E
Not skilled
persons
Not possible
C and D, or E
C and D, or E
C and D, or E
controls. When the network input is back, the bar closes resetting all controls
OFF - The bar carries out the normal working until the battery is exhausted.
DIP 10 - Working after black-out WITHOUT batteries.
ON - The bar closes
OFF - The bar stops in the point where the black-out happened.
S1
PROG. Key for the programming.
TERMINAL BOARD J1
SEC.TRANSF.
Connection for secondary transformer (carried out in the factory).
CONNECTOR J2
MOTOR Connection MOTOR and ENCODER (carried out in the factory).