Output charts water
SWX CE
Type
Airflow
[m³/h]
SWXCE12
2100
SWXCE22
4200
Type
Airflow
[m³/h]
SWXCE12
2100
SWXCE22
4200
Type
Airflow
[m³/h]
SWXCE12
2100
SWXCE22
4200
6
Incoming / outgoing water temperature 90/70 °C
Air temp. in = +5 °C
Output
Air temp.
Water flow
out
[kW]
[°C]
[l/s]
29,5
45,2
0,37
56,6
43,6
0,70
Incoming / outgoing water temperature 80/60 °C
Air temp. in = +5 °C
Output
Air temp.
Water flow
out
[kW]
[°C]
[l/s]
25,2
39,4
0,31
48,5
38,1
0,60
Incoming / outgoing water temperature 60/40 °C
Air temp. in = +5 °C
Output
Air temp.
Water flow
out
[kW]
[°C]
[l/s]
16,4
27,4
0,20
32,2
26,9
0,40
SWX CE
Air temp. in = +15 °C
Pressure
Output
drop
[kPa]
[kW]
11,9
24,8
30,3
47,7
Air temp. in = +15 °C
Pressure
Output
drop
[kPa]
[kW]
9,0
20,6
23,1
39,8
Air temp. in = +15 °C
Pressure
Output
drop
[kPa]
[kW]
4,2
11,9
11,2
23,7
Air temp.
Water
Pressure
out
flow
drop
[°C]
[l/s]
[kPa]
50,1
0,31
8,6
48,8
0,59
22
Air temp.
Water
Pressure
out
flow
drop
[°C]
[l/s]
[kPa]
44,2
0,26
6,1
43,2
0,49
15,9
Air temp.
Water
Pressure
out
flow
drop
[°C]
[l/s]
[kPa]
31,9
0,15
2,3
31,8
0,29
6,4

Publicité