INSTALLATION
APPLICATION REQUIREMENTS: Available to all commercial door operators using the Logic 5 control board.
To avoid SERIOUS personal INJURY or DEATH from electrocution, DISCONNECT electrical power to operator BEFORE proceeding.
REMOVE EXISTING BOARD
1. Disconnect power to operator.
2. Remove all wires from the existing board:
• Control Wiring Terminal Block
• System Wiring Connector (J3)
NOTE: Remember location of all wiring connections for
reinstallation.
3. Remove the coaxial cable from the board F connector.
4. Remove any installed option cards from their corresponding
slots from the board.
5. Remove the board from its four mounting posts.
WIRING POWER AND CONNECTION SETTINGS
Before matching any connection settings, make sure the power
supply is the correct voltage, phase, frequency, and amperage
compatible with your operator.
1. Remove the new board from the protective bag.
2. Match settings from existing board to the new board:
• 1-Phase and 3-Phase Jumper
For 3-Phase Operators Only: DO NOT move the 3-Phase
jumper until installation and specifi ed instructions following
Step 6 are completed.
• Motor Direction Jumper
• Selector Dial
NOTE: The following information is stored within the fi rmware and
will need to be re-programmed if the fi rmware is upgraded with
the board:
• All Remote Controls (On Board Receiver Only)
• Timer-to-Close
• Maximum Run Timer
• Maintenance Alert System
• Up and Down Mid Stops
• Pre-Warning Timer when the TLSCARD option card is used
• Dynamic Brake for models N4/N4X only when AUXCARD is
used.
WARNING
WARNING
WARNING
INSTALL NEW BOARD
1. Place the new board into the operator. Position the board onto
mounting posts pressing firmly to ensure posts are completely
through mounting holes.
2. Reconnect the coaxial cable to the board F connector.
3. Reconnect all wires to the main board control wiring terminal
block.
4. Install all option cards into the slots on the board.
5. Make sure the electrical box is clear of all debris and tools.
AVERTISSEMENT
6. Reconnect power to the operator and verify operation.
3-PHASE OPERATORS ONLY
AVERTISSEMENT
NOTE: DO NOT activate the operator until the following steps
have been completed:
1. Turn the SELECTOR DIAL to PROG (programming).
2. Move the PHASE jumper from the 1-Phase position to the
3-Phase position.
3. Return the SELECTOR DIAL to desired mode of operation.
Refer to pages 3-10 for programming and settings as necessary.
SPECIAL PROGRAMMING IS REQUIRED FOR N4/N4X
MODELS USING AN AUXCARD. THIS SETS THE DYNAMIC
BRAKE FOR THE MOTOR. FOLLOW THESE INSTRUCTIONS
PRIOR TO RUNNING THE OPERATOR.
1. Turn the SELECTOR DIAL to OPTN.
2. Press and release the MAS button.
3. Press and release the MID button. The MAS LED will blink
ADVERTENCIA
6 times.
4. Turn SELECTOR DIAL back to desired wiring type.
ADVERTENCIA
LOGIC BOARD (L5)
REPLACEMENT KIT
K001D8075-1

Publicité

Table des Matières
loading

Sommaire des Matières pour Chamberlain LiftMaster K001D8075-1

  • Page 1 LOGIC BOARD (L5) REPLACEMENT KIT K001D8075-1 INSTALLATION WARNING APPLICATION REQUIREMENTS: Available to all commercial door operators using the Logic 5 control board. WARNING WARNING To avoid SERIOUS personal INJURY or DEATH from electrocution, DISCONNECT electrical power to operator BEFORE proceeding. REMOVE EXISTING BOARD INSTALL NEW BOARD 1.
  • Page 2: Introduction To Programming

    PROGRAMMING INTRODUCTION TO PROGRAMMING Many programmable functions require that a LiftMaster Entrapment Protection (LMEP) device be installed in order to function. Refer to the Entrapment Protection section. Before programming the logic board, set the operator’s open and LOGIC BOARD PUSH BUTTONS (OPEN, CLOSE, STOP) close limits.
  • Page 3: Determine And Set Wiring Type

    DETERMINE AND SET WIRING TYPE Read the descriptions of the different wiring types to determine which setting will be correct for each application. Once the wiring type is determined, set the selector dial accordingly. LIFTMASTER MONITORED ENTRAPMENT PROTECTION (LMEP) LIFTMASTER MONITORED ENTRAPMENT PROTECTION (LMEP) DEVICE IS REQUIRED DEVICE IS RECOMMENDED A LiftMaster Entrapment Protection (LMEP) device is...
  • Page 4: Programming Remote Controls

    PROGRAMMING REMOTE CONTROLS WARNING WARNING To prevent possible SEVERE INJURY or DEATH: CAUTION • Activate door ONLY when it can be seen clearly, is properly • Install a LiftMaster Monitored Entrapment Protection (LMEP) adjusted and there are no obstructions to door travel. device.
  • Page 5 PROGRAMMING REMOTE CONTROLS REMOTE CONTROL PROGRAMMING FEATURE NOTE: The following programming requires a LiftMaster Monitored Entrapment Protection (LMEP) device. Program Remote Controls from the 3-button control station Your Security✚ 2.0™ or dip switch remote control can be (3BCS). programmed to operate as a 3-button wireless control station: This feature allows the user to add additional remote controls the large button will open the door, the middle button will close from the 3BCS.
  • Page 6: Maintenance Alert System (Mas)

    ® PROGRAMMING MYQ DEVICES (OPTIONAL) To Program MyQ Devices: 2. Press and hold the MAS button for 5 seconds. The RADIO LED 1. To enter programming mode, press and release the RADIO button will flash for approximately 5 seconds and the RADIO LED will on the logic board (the RADIO LED will light).
  • Page 7: Open Mid Stop

    OPEN MID STOP Feature: The Mid Stop feature is to open the door to a preset point prior to the fully open position. Benefit: The door opens to a midpoint between open and close SELECTOR DIAL reducing heating and cooling costs. The door will not cycle fully, providing longer door and operator life.
  • Page 8: Car Dealer Mode

    TIMER-TO-CLOSE PROGRAM TIMER-TO-CLOSE BY EXAMPLE (METHOD 2): TO PROGRAM: 1. Close the door. SELECTOR DIAL 2. Turn the selector dial to PROGRAM. 3. Press and hold TIMER button for 5 seconds until OPEN and OLS flashes then release. FSTS 4. Press and release the OPEN button and wait for the door to reach full open or mid stop position.
  • Page 9: Maximum Run Timer (Mrt)

    MAXIMUM RUN TIMER (MRT) Feature: The operator can learn the time it takes to open or close SELECTOR DIAL the door plus and an additional 10 seconds. Benefit: If the operator does not meet its open or close limit within the set time it will stop, limiting damage to the door and operator.
  • Page 10: Maintenance Schedule

    WARNING WARNING MAINTENANCE MAINTENANCE SCHEDULE CAUTION WARNING WARNING For use with Maintenance Alert System. Check at the intervals listed in the following chart: To avoid SERIOUS personal INJURY or DEATH: • Disconnect electric power BEFORE performing ANY adjustments or maintenance. •...
  • Page 11: Retrait Du Tableau Existant

    NÉCESSAIRE DE REMPLACEMENT DE TABLEAU DE CONTRÔLE (L5) K001D8075-1 INSTALLATION EMENT AVERTISSEMENT EXIGENCES D'APPLICATION : Disponible pour tous les actionneurs de porte commerciaux utilisant le tableau de contrôle Logic 5. AVERTISSEMENT AVERTISSEMENT Pour éviter des BLESSURES personnelles SÉRIEUSES ou la MORT par électrocution, DÉCONNECTER l’alimentation électrique à l’actionneur AVANT de procéder.
  • Page 12: Introduction À La Programmation

    PROGRAMMATION INTRODUCTION À LA PROGRAMMATION Plusieurs fonctions programmables exigent qu'un dispositif de Protection contre le piégeage LiftMaster (LMEP) soit installé pour fonctionner. Se référer à la section Protection contre le piégeage. Avant de programmer la carte logique, configurer les fins de course BOUTON-POUSSOIRS DE LA CARTE LOGIQUE (OPEN (OUVRIR), d'ouverture et de fermeture de l'ouvre-porte.
  • Page 13: Détermination Et Configuration Du Type De Câblage

    DÉTERMINATION ET CONFIGURATION DU TYPE DE CÂBLAGE Lire les descriptions des différents types de câblage pour déterminer quelle configuration sera correcte pour chaque application. Lorsque le type de câblage est déterminé, configurer le cadran de réglage en conséquence. UN DISPOSITIF DE PROTECTION CONTRE LE PIÉGEAGE AVEC UN DISPOSITIF DE PROTECTION CONTRE LE PIÉGEAGE AVEC SURVEILLANCE LIFTMASTER (LMEP) EST NÉCESSAIRE SURVEILLANCE LIFTMASTER (LMEP) EST RECOMMANDÉ...
  • Page 14: Programmation Des Télécommandes

    PROGRAMMATION DES TÉLÉCOMMANDES AVERTISSEMENT AVERTISSEMENT Pour empêcher une BLESSURE GRAVE ou une MORT possible : • Activer la porte SEULEMENT lorsqu'elle peut être vue clairement, qu'elle est correctement ajustée et qu'il n'y a aucune obstruction au • Installer un dispositif de Protection contre le piégeage avec ATTENTION déplacement de la porte.
  • Page 15 PROGRAMMATION DES TÉLÉCOMMANDES REMARQUE : La programmation suivante nécessite un dispositif de FONCTION DE PROGRAMMATION DE LA TÉLÉCOMMANDE Protection contre le piégeage avec surveillance LiftMaster (LMEP). Programmation de télécommandes à partir de la station de commande Votre télécommande Security✚ 2.0 ou DIP programmable peut être à...
  • Page 16: Programmation Des Dispositifs Myq

    PROGRAMMATION DES DISPOSITIFS MYQ (FACULTATIVE) Pour programmer les dispositifs MyQ : 2. Pressez et maintenezenfoncé le bouton MAS pendant 5 secondes. Le bouton DEL RADIO clignotera pendant approximativement 5 secondes, 1. Pour accéder au mode de programmation, appuyez sur le bouton puis s’éteindra. RADIO de la carte logique (le bouton DEL RADIO clignotera).
  • Page 17: Ouverture À Mi-Course

    OUVERTURE À MI-COURSE Caractéristique : La fonction mi-course est pour ouvrir la porte à un Pour annuler le réglage de mi-course, placer le cadran de réglage à PROG point prédéterminé avant la position entièrement ouverte. puis appuyer et tenir le bouton MID durant 5 secondes. La DEL MID clignotera rapidement et s'éteindra lorsque la mi-course aura été...
  • Page 18: Mode Concessionnaire Automobile

    MINUTERIE DE FERMETURE PROGRAMMATION DE LA MINUTERIE DE FERMETURE PAR EXEMPLE (MÉTHODE 2) : POUR PROGRAMMER : 1. Fermer la porte. CADRAN DE RÉGLAGE 2. Tourner le cadran de réglage à PROGRAM. 3. Appuyer et tenir le bouton TIMER (minuterie) durant 5 secondes jusqu'à...
  • Page 19: Minuterie De Fonctionnement Maximal (Mrt)

    MINUTERIE DE FONCTIONNEMENT MAXIMAL (MRT) Caractéristique : L'ouvre-porte peut apprendre le temps nécessaire pour ouvrir ou fermer la porte plus ajouter un 10 secondes supplémentaires. CADRAN DE RÉGLAGE Avantage : Si l'ouvre-porte n'atteint pas la fin de course ouvert ou fermée dans le temps configuré, il s'arrêtera, limitant le dommage à...
  • Page 20: Périodicités D'entretien

    Inspecter les plaquettes de frein et remplacer l'ensemble de frein si nécessaire. REMARQUE : Votre ouvre-porte peut sembler différent de l'ouvre-porte montré. REMARQUE : Pour les instructions de dépannage, référez-vous au Manuel d’Installation. © 2014, The Chamberlain Group, Inc. All Rights Reserved 01-36820 Tous droits réservés...

Table des Matières