53
PA 4
54
PB 1
55
PB 2
56
PB 3
57
PB 4
58
Probe B4
59
Probe B5
7. 1
WRITE ANALOG DATA
ADDRESS
DATA ITEM DESCRIPTION
145
ColdSet
146
HotSet
147
Tot.Diff.
148
S.Hot R
149
D.Tot. R
150
2nd C. Set
151
2nd H. Set
Cold operating mode set
Hot operating mode set
Total differential set for thermostat
Hot operating mode recuperator control set
Total differential set for recuperator control thermostat
Second cold set
Second hot set
High pressure circuit 4
Low pressure circuit 1
Low pressure circuit 2
Low pressure circuit 3
Low pressure circuit 4
Temperature common evaporator outlets
Temperature common condenser outlets
RANGE
-10.0 to +20.0 °C
30.0 to 50.0 °C
03.0 to 10.0 °C
30.0 to 50.0 °C
03.0 to 10.0 °C
-10.0 to +20.0 °C
30.0 to 50.0 °C