Miscellaneous
Delay of output signals after start-up
Input signal on DI1. Function:
0=not used. 1=status on DI1. 2=door function
with alarm when open. 3=door alarm when open.
4=defrost start (pulse signal). 5=ext.main switch.
6=night operation 7=change reference (activate
r40). 8=alarm function when closed. 9=alarm func-
tion when open. 10=case cleaning (pulse signal).
11=forced cooling. 12=S5B
Network address
On/Off switch (Service Pin message)
IMPORTANT! o61 must be set prior to o04
Access code 1 (all settings)
Used sensor type (Pt /PTC/NTC)
Display step = 0.5 (normal 0.1 at Pt sensor)
Max hold time after coordinated defrost
Select signal for display view. S4% (100%=S4,
0%=S3)
Input signal on DI2. Function:
(0=not used. 1=status on DI2. 2=door function
with alarm when open. 3=door alarm when open.
4=defrost start (pulse-pressure). 5=ext. main switch
6=night operation 7=change reference (activate
r40). 8=alarm function when closed. 9=alarm func-
tion when open. 10=case cleaning (pulse pressure).
11=forced cooling . 12=coordinated defrost)
Configuration of light function (relay 4)
1=ON during day operation. 2=ON / OFF via data
communication. 3=ON follows the DI-function,
when DI is selected to door function or to door
alarm
Activation of light relay (only if o38=2)
Rail heat On time during day operations
Rail heat On time during night operations
Rail heat period time (On time + Off time)
Case cleaning. 0=no case cleaning. 1=Fans only.
2=All output Off.
Selection of EL diagram. See overview page 1
Transfer a set of pre-settings See overview page 7.
Access code 2 (partly access)
Save the controllers present settings to the pro-
gramming key. Select your own number.
Load a set of settings from the programming key
(previously saved via o65 function)
Replace the controllers factory settings with the
present settings
Service
Status codes
Temperature measured with S5 sensor
Status on DI1 input. on/1=closed
Temperature measured with S3 sensor
Status on night operation (on or off ) 1=closed
Temperature measured with S4 sensor
Thermostat temperature
Read the present regulation reference
Status on DI2 output. on/1=closed
Temperature shown on display
Measured temperature for alarm thermostat
Status on relay for cooling
Status on relay for fan
Status on relay for defrost
Status on relay for rail heat
Status on relay for alarm
Status on relay for light
Temperature measured with S5B sensor
Status of night time cover detection (On = night
time cover has been detected)
*) Can only be set when regulation is stopped (r12=0)
**) Can be controlled manually, but only when r12=-1
***) With access code 2 the access to these menues will be limited
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep upper and lower button depressed at the same time as you recon nect the supply voltage
6
o01
o02
o03
o04
o05
o06
o15
o16
o17
o37
o38
o39
o41
o42
o43
***
o46
*
o61
1
2
3
*
o62
***
o64
o65
o66
o67
S0-S33
***
u09
u10
***
u12
***
u13
***
u16
u17
u28
u37
u56
u57
**
u58
**
u59
**
u60
**
u61
**
u62
**
u63
***
u75
U08
Instructions RI8NK459 © Danfoss 06/2015
0 s
600 s
5 s
1
12
0
0
240
0
OFF
ON
OFF
0
100
0
Pt
ntc
Pt
no
yes
no
0 min
60 min
20 min
0%
100%
100%
0
12
0
1
3
1
OFF
ON
OFF
0%
100%
100%
0%
100%
100%
6 min
60 min
10 min
0
2
0
1
3
1
0
10
0
0
100
0
0
25
0
0
25
0
OFF
On
OFF
Fault code display
E 1
Fault in controller
E 6
Change battery + check clock
E 25
S3 sensor error
E 26
S4 sensor error
E 27
S5 sensor error
E 37
S5B sensor error
Alarm code display
A 1
High temperature alarm
A 2
Low temperature alarm
A 4
Door alarm
A 5
Max. Hold time
A 8
High Temp. Alarm S3
A 9
Low Temp. Alarm S3
A 15
DI 1 alarm
A 16
DI 2 alarm
A 45
Standby mode
A 59
Case cleaning
A 81
Switched S3 and S4 sensors?
Status code display
S0
Regulating
S 1
Waiting for end of the coordinated
defrost
S 2
ON-time Compressor
S 3
OFF-time Compressor
S 4
Drip-off time
S 10
Refrigeration stopped by main
switch
S 11
Refrigeration stopped by thermostat
S 14
Defrost sequence. Defrosting
S 15
Defrost sequence. Fan delay
S 17
Door open (open DI input)
S 20
Emergency cooling
S 25
Manual control of outputs
S 29
Case cleaning
S 30
Forced cooling
S 32
Delay of output at start-up
non
The defrost temperature cannot
be displayed. There is stop based
on time
-d-
Defrost in progress
PS
Password required
EKC 202D1